TROUBLESHOOTING
bb 23
11
Thermo Temp. of
Remote Control
Switch
,QGLFDWLRQRQ0LFUR&RPSXWHU,QSXW2XWSXW
C1
Z
12
Micro Computer
Input/Output in Indoor
Unit
C2
-
13
Micro Computer
Input/Output in
Outdoor Unit
,QGLFDWLRQRI8QLW6WRSSDJHFDXVH
d1 01
14
Cause of Stoppage
$EQRUPDOLW\2FFXUUHQFH&RXQWHU
E1 01
15
Abnormality
Occurrence Times
E2 00
16
Instantaneous Power
Failure Occurrence
Times in Indor Unit
E3 00
17
Transmission Error
Occurrence Times
between Remote Control
Switch and Indoor Unit
E4 00
18
Abnormality
Occurrence Times on
Inverter
,QGLFDWLRQRI$XWRPDWLF/RXYHU&RQGLWLRQ
F1 00
19
Louver Sensor
to next page
00
Operation OFF, Power OFF
01
Thermo - OFF (Note 1)
02
Alarm (Note 2)
03
Freeze Protection, Overheating Protection
05
Instantaneous Power Failure at Outdoor Unit, Reset (Note 3)
06
Instantaneous Power Failure at Indoor Unit, Reset (Note 4)
07
Stoppage of Cooling Operation due to Low Outdoor Air
Temperature, Stoppage of Heating Operation due to High
Outdoor Air Temperature
08
Compressor Quantity Changeover, Stoppage (HP
8)
09
Demand of 4-Way Valve Changeover Stoppage (FX Only)
10
Demand, Enforced Stoppage
11
Retry due to Pressure Ratio Decrease
12
Retry due to Low Pressure Increase
13
Retry due to High Pressure Increase
14
Retry due to Abnormal Current of Constant Compressor (HP
8)
15
Retry due to Abnormal High Temperature of Discharge Gas,
Excessively Low Suction Pressure
16
Retry due to Decrease of Discharge Gas Superheat
17
Retry due to Inverter Tripping
18
Retry due to Voltage Decrease
19
Expansion Valve Opening Change Protection
20
Operation Mode Changeover of Indoor Unit (Note 5)
Note 1: Explanation of Terms
Thermo-ON:
A condition than an Indoor Unit is requesting
compressor to operate.
Thermo - OFF: A condition than an Indoor Unit is not
requesting compressor to operate.
Note 2: Even if stoppage is caused by "Alarm", "02" is not always
indicated.
Note 3: If transmission between the inverter printed circuit board and
the control printed circuit board is not performed during 30
seconds, stoppage is d1-05 cause and the alarm code "04" may
be indicated.
Note 4: If transmission between the Indoor Unit and the Outdoor Unit is
not performed during 3 minutes, Indoor Units are stopped.
In this case, stoppage is d1-06 cause and the alarm code "03"
may be indicated.
Note 5: In the FSG and FS3 system "20" will be indicated at the
difference mode between Indoor Units.
Countable up to 99.
Over 99 times, "99" is always indicated.
Note 1: If a transmitting error continues for 3 minutes, one is added to
the occurrence times.
Note 2: The memorized data can be cancelled by the method indicated
in 1.3.1. "Self-checking of PCBs using Remote Control Switch"
00
: Normal
FF
: Abnormal
YH2
Y52H
Operation
Alarm
Heating Thermo-ON
Coding Thermo-ON
Not
shown
Y20A
Y20B
Y211
Y52C1
Y52C2
Outdoor Fan
Symbols with a letter Y
are relays on PCB
Not
shown
Y212
YMS
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...