TROUBLESHOOTING
Alarm Code
45
Activation to Protect System from Excessively High Discharge Pressure
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the compressor is operated under the conditions higher than 2.7 MPa
(27 kg/cm²G) of discharge pressure ( in case of frequency 30Hz, Pd is higher than 2.5 MPa (25 kg/cm²G)
and its occurrence is more than 3 times including 3 in one hour).
Is there a leakage of the solenoid
valves SVA?
Yes
Replace the solenoid valve SVA if
faulty.
No
Is the outdoor unit stop valve closed?
Yes
Open the stop valve.
No
Is the high-pressure sensor good?
No
Check connection of the circuit board
connector. Replace the high-pressure
sensor if faulty.
Yes
Yes
Are ex. valves fully closed and locked?
Check the circuit board and connection
of the circuit board connector. Replace
the electronic expansion valves if faulty.
No
Check the outdoor electronic expansion valve
during cooling and the indoor electronic expansion
valve during heating.
Are electric wiring and refrigerant
piping between the indoor and
outdoor unit incorrectly connected?
Yes
Correctly connect it..
No
Check if indoor or outdoor intake air
temperature is too high.
No In the case of H-LINK connection,
check the refrigeration cycle setting on
the PCB of outdoor unit and indoor unit.
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Leakage of Solenoid Valve
SVA (Outdoor Unit)
Check outlet temp. of
solenoid valve, SVA.
Check connection. Replace
solenoid valve SVA if faulty.
Closed Stop Valve
Check stop valve.
Open stop valve.
Abnormal High Pressure
Sensor
Check connectors for
PCB.
Replace pressure sensor if
faulty.
Excessively High Indoor Unit
and Outdoor Unit Inlet Air Temp.
Check thermistor for indoor
unit and outdoor unit inlet air
temp.
Replace thermistor if
faulty.
Incorrect Connection between
Indoor Unit and Outdoor Unit
.
Check electrical system and
ref. cycle.
Correctly Connect.
Excessively
High Discharge
Pressure
Locked Ex. Valve with Fully
Closed Opening
Check connector for PCB.
Repair connector for PCB or
ex. valve. Replace it if faulty.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...