1
TROUBLESHOOTING
49
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Excessively High or Low
Voltage of Power Source
operate within
380-145V±10%(50Hz)
380V±10%(60Hz)
220V±10%(60Hz)
Imbalance Among Phase
at Power Source
Adjust voltage between
each phase.
Excessively Large Running
Current of Compressor Motor
Excessively High
Discharge Pressure
Check for causes.
Melted Fuse for Power
Source
Replace the fuses.
Looseness of Screws for
Power Source
Tightly fix screws.
Single Phase Operation
Deterioration of Contact of
Magnetic Switch for
Compressor
Replace magnetic
contactor.
Seizure of Compressor
Bearing
Locked-up?
Replace compressor.
Insulation Failure of
Compressor Motor
Measure insulation
resistance.
Replace compressor.
Fault
Check continuity during
stoppage.
Replace CT when faulty.
Incorrect
Connection
Measure resistance by
tester.
Remove looseness and
replace connectors.
Overcurrent of
Compressor
Motor
Faulty CT
Incorrect
Wiring
Check wiring.
Correctly wiring.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...