1
TROUBLESHOOTING
45
Alarm Code
31
Incorrect Capacity Setting or Combined Capacity
between Indoor Units and Outdoor Unit
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the capacity setting dip switch, DSW2 on the outdoor unit PCB1, is not
set (all the settings from #1 to #3 are OFF) or mis setting.
This alarm code is indicated when the total indoor unit capacity is smaller than 50% or greater than 150% of
the combined outdoor unit capacity.
Are #1-#3 of DSW2 on the
outdoor unit PCB1 set correctly?
No
Set the capacity for PCB1.
Yes
Are #1-#4 of DSW3 on the indoor
unit PCB set correctly?
No
Set the capacity for PCB.
Yes
Are the setting of DSW1 on the
outdoor unit PCB1 and the setting of
DSW5 on the indoor unit PCB totally
same in a refrigerant cycle?
No
Set them correctly
Yes
Total capacity of the indoor units is
wrong.
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Incorrect Capacity Setting of Indoor Unit
Check combination of
indoor units and capacity
setting on PCB.
Correctly set dip switch,
DSW3.
Incorrect Capacity Setting of Outdoor Unit
Check capacity setting on
outdoor unit PCB.
Correctly set dip switch,
DSW2.
Total Indoor Unit Capacity Connected to the Outdoor
Unit is Beyond Permissible Range
Check outdoor unit model
by calculating total indoor
units capacity.
Ensure that total indoor
unit capacity is from 50%
to 130%.
Refrigeration Cycle Setting of Outdoor Unit and Indoor
Unit is Different.
Check refrigeration cycle
setting on outdoor unit
PCB and indoor unit PCB.
Set them correctly.
Combination
Combined Indoor Unit
Outdoor Unit Model
Total Quantity
Total Capacity (HP)
Notes
RAS-5FSG, RAS-5FS3
2-8 sets *1)
2.5-6.5
RAS-8FSG, RAS-8FS3
4.0-10.4
RAS-10FSG, RAS-10FS3
2-12 sets
5.0-13.0
*1): If the capacity of one indoor unit is the same as of
the outdoor unit, the system can be operated.
RAS-16FSG, RAS-16FS3
2-13(16) sets *2)
8.0-20.8
RAS-20FSG, RAS-20FS3
2-16 sets
10.0-26.0
*2): In case of changing the indoor unit capacity from
1.0HP or 1.5HP to 1.3HP by dip switch setting.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...