TROUBLESHOOTING
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Ref. Cycle is Different from
the Electrical System
Check ref. cycle and
electrical system.
Repair wiring.
Overcharged Refrigerant
Measure pressure. (Refer to
Figure in Test Run of TC.)
Correctly charge
refrigerant.
Faulty Ex. Valve
Refer to 1.3.6.
Replace ex. valve if faulty.
Fault
Replace PCB and check
operation.
Replace PCB if faulty.
Faulty PCB
Disconnected
Wires for Ex.
Valve Control
Check connections.
Repair wiring connection.
Fault
Measure resistance.
Replace thermistor if
faulty.
Incorrect
Mounting
Check mounting state.
Correctly mount
thermistor.
Decrease of
Discharge Gas
Superheat
Faulty
Discharge
Gas
Thermistor
Incorrect
Connection
Check connections.
Remove looseness,
replace connector or
repair connections
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...