1
TROUBLESHOOTING
29
Alarm Code
07
Decrease of Discharge Gas Superheat
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
In the case that the discharge gas superheat less than 10 deg. at the top of the compressor is maintained
for 30 minutes, retry operation is performed. However, when the alarm occurs again within 90 minutes, this
alarm code is indicated.
Is the thermistor on top of
compressor good? *1)
No
Faulty Thermistor
Yes
Is the thermistor installed
correctly on the compressor?
No
Install it correctly.
Yes
Is it at cooling or heating
mode when the alarm has
occurred?
Heat
Heating Operation
Cool
Cooloing Operation
Check the high-pressure and
compressor discharge gas
temperature and calculate superheat
value by outdoor unit PCB.
Check the discharge pressure and
compressor discharge gas
temperature and calculate superheat
value by outdoor unit PCB.
No
Is superheat value
under10 °C?
Superheat: under 10 °C?
No
Yes
Yes
Is the opening of the outdoor
unit heat exchanger's
expansion valve under 12%?
No
Yes
Remove sudden changes
of load like short path of
outgoing air to the air
intake of the outdoor unit,
or the cause of frequent
thermo- ON/OFF.
Match the
refrigerant piping
and electric wiring.
No
Are the refrigerant
piping and electric
wiring matching?
Are the connector (CN10 and
CN11 of PCB1) of the outdoor
unit heat exchanger’s electric
expansion valve connected
properly?
No
Plug the connector CN10
and CN11 of PCB1
properly.
Yes
Yes
Is refrigerant correctly
charged?
No
Charge correct refrigerant
volume.
Refer to Chapter 12 of TC
Plug the connector
properly.
No
Is the connector on
indoor unit PCB for ex.
valve connected
properly?
Yes
Is gas leaking?
No
Check the ex. valve.
Yes
Repair leaks of gas. Correctly
charge refrigerant.
*1): Refer to "Characteristics of Thermistor" of page 1-42.
Position of the Thermistor
Model
RAS-[HP]FSG/FS3
Thermistor
position (a)
Thermis-
tor ref.
Display
5
8
10
16
20
THM8
ód1
Inverter
THM9
ód2
fix compressor
THM12
ód3
THM13
ód4
No. of compressors
1
2
2
3
4
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...