1
28
TROUBLESHOOTING
Alarm Code
06
Excessively Low or High Voltage for Inverter
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when voltage between terminal ”P” and ”N” of transistor module (IPM) is
insufficient and its occurrence is three times in 30 minutes. In the case that the occurrence is smaller than 2
times, retry is performed.
Restart operation.
In case of 380V-415V 50Hz:
Is the power supply voltage 380V ±10%
or 415V ±10%?
No
Check wiring and cable
capacity.
Yes
In case of 380V-415V 50Hz:
Is the voltage over 323V during operation?
No
Yes
Does the voltage fall during
operation by operation of other
apparatus?
Yes
No
Frequency can
increase higher
than 60Hz.
Does LED2 on PCB3 ON after
compressor’s electromagnetic
switches (CMC) turn on?
Yes
How is
compressor
operation?
Compressor stops
immediately. (lower
than 30Hz)
Faulty PCB3 for
Inverter. Replace it.
No
No
Compressor stops
when frequency
increase. (Approx..
30Hz to 60Hz)
Is connection correctly between
PCB3 and transistor module?
Connect Correctly
Yes
Be careful especially because
of high voltage.
(Loose Wiring
Change of color)
Is the DC voltage over 560V?
Yes
Check capacitors
(CB1, 2).
No
Fault
Replace capacitors.
No
Normal
Capacitors have high voltage.
Be careful especially. *1)
PCB3 is faulty.
Replace it.
Check the wiring, diode
module (DM) and
capacitors (CB1, 2). *2)
*1): If capacitor has high voltage, perform the high voltage discharge work refer to item 1.3.6.
*2): Checking procedures of diode module is indicated in item 1.3.6.
*3): DC voltage measuring position:
IPM "P" Terminal to "+" Terminal of Tester, "N" Terminal to "–" Terminal of Tester Measuring Position: DC 1000V
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...