1
14
TROUBLESHOOTING
1.1.7 ABNORMALITIES OF DEVICES (Cont.)
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Clogging of Outdoor Unit
Heat Exchanger?
Remove Clogging.
Obstacles at Inlet or outlet
of outdoor unit heat
exchanger.
Remove obstacles.
Is service space for
outdoor unit sufficient?
Secure service space.
Insufficient
Air Flow to
Outdoor
Unit Heat
Exchanger
Correct Fan Speed?
Replace fan motor.
Short-Circuited Air to
Outdoor Unit?
Remove cause of short-
circuited air.
Excessively
High Air
Temp. to
Outdoor
Unit Heat
Exchanger
Any Other Heat Load near
Outdoor Unit?
Remove heat source.
Excessively
Charged
Refrigerant
Check each Temp.
Correctly Charge
Refrigerant.
Non-
Condensed
Gas in Cycle
Check each Temp. and
Pressure.
Charge Refrigerant after
Vacuum Pumping.
Clogging of
Discharge
Piping
Check for Clogging.
Remove Clogging.
Check for clogging.
Remove clogging.
Check for connecting cord
and connector.
Replace connector.
Is there operation sound
from coil?
Replace coil.
Is thermistor on
compressor normal?
Replace thermistor.
Excessively
High
Discharge
Pressure
Failure or
Malfunction
of
Expansion
Valve
Is thermistor installed
correctly on compressor?
Correctly install it.
Malfunction or Internal
Leakage of 4-Way Valve
Check temp. difference at
inlet and outlet of 4-way
valve.
Replace 4-way valve.
Failure of
Bypass
Solenoid
Check for Leakage of
Solenoid Valve.
Replace Solenoid Valve.
Excessively
High
Suction
Pressure
Malfunction or
Internal
Leakage of 4-
Way Valve
Check Temp. Difference
between Inlet and Outlet
of 4-Way Valve.
Replace 4-Way Valve.
Insufficient
Cooling
Operation
Discharge Temp. of Indoor
Unit Is Unstable.
Check for expansion valve
of indoor unit in the same
system.
Replace failed expansion
valve of indoor unit.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...