4
16
OPTIONAL FUNCTION
n
Setting Items of Optional Functions
No.
Items
Optional Functions
Individual
Setting
Setting
Condition
Contents
®
b1
Removal of Heating Temperature
Calibration
00
01
Not Available
Available
¯
b2
Circulation Function at Heating
Thermo-OFF
00
01
Not Available
Available
°
b3
Enforced 3 Minutes Minimum
Operation Time of Compressor
00
01
Not Available
Available
±
b4
Change of Filter Cleaning Time
00
01
02
03
04
Standard
100 hours
1200 hours
2500 hours
Not Indication
²
b5
Fixing of Operation Mode
5
00
01
Not Available
Available
³
b6
Fixing of Setting Temperature
5
00
01
Not Available
Available
´
b7
Fixing of Operation as Exclusive
Cooling Unit
5
00
01
Not Available
Available
µ
b8
Automatic COOL/HEAT
5
00
01
Not Available
Available
¶
b9
Fixing of Air Volume
5
00
01
Not Available
Available
·
C8
Thermistor of Remote Control Switch
00
01
02
Control by Indoor Suction Thermistor
Control by Remote Control Thermistor
Control by Average
¸
F1
Automatic Setting for OFF Timer
5
00
01
02
~
23
24
No Function
OFF Timer by 1 Hour
OFF Timer by 2 Hour
OFF Timer by 23 Hours
OFF Timer By 24 Hours
NOTES:
As for optional functions with "
5
"
at the individual
setting, only when the "All Rooms" is selected to set the
optional function, the setting condition can be changed.
As for the items not indicated in the above table, the
optional function is not available. Do not change the
setting.
4.3.5.
OPTIONAL FUNCTIONS OF REMOTE
CONTROL SWITCH
®
Removal of Heating Temperature Calibration
This function is utilized when the temperature settings of
the remote control switch and the suction air temperature of
the indoor unit are required to be equal.
In standard heating operation, the suction air temperature
is higher than the room temperature, therefore the suction
air temperature is calibrated -4°C.
(Indicated Setting Temperature = Suction Air Temperature
-4°C
Return to 0 °C) This is useful when the thermistor at
the suction side of an indoor unit is removed and installed
in another place. The indicated setting temperature and the
suction air temperature after removal of heating
temperature calibration are as shown beside.
Activating Temperature (°C)
When Heating / For Comp.
Indicated
Temperature
When
Cooling
Standard
After Removal
ON
-
22
18
18
OFF
-
24
20
ON
22
24
20
20
OFF
20
26
22
ON
24
26
22
22
OFF
22
28
24
ON
26
28
24
24
OFF
24
30
26
ON
28
30
26
26
OFF
26
32
28
ON
30
30
28
28
OFF
28
32
30
ON
32
30
30
30
OFF
30
32
32
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...