OPTIONAL FUNCTION
4.2.3.
FIXING OPERATION MODE
In the case that the fixing input terminals of the operation
mode on the outdoor PCB are short-circuited, the operation
mode can be fixed at the cooling or heating mode.
Short-circuit between Terminals 1 and 2 of CN17: Fixed
Heating Mode
Short-circuit between Terminals 2 and 3 of CN17: Fixed
Cooling Mode
This fixed mode will be shared in the RCS. During this fixed
heating (or cooling) mode, no cooling (or heating) operation
is available. If cooling (or heating) mode is selected, the
indoor units under the cooling or dry operation (or heating
operation) will be changed to the Thermo-OFF condition
during this mode, and an alarm code of "20" appears.
The stoppage cause code "d1" will be "20"
Wiring Diagram Example of Fixing Operation Mode:
4.2.4.
SNOW SENSOR
In the case that the input terminals of the snow sensor are
short-circuited during compressor stoppage, all the outdoor
fan motors are operated at the full speed. However, if the
compressor is called for compressor operation, the fan
operation is changed to the normal operation. If the input
terminal is opened, the fan(s) is stopped. This function
protects the outdoor units from a condition covered with
snow.
Wiring Diagram Example of Snow Sensor
Table 4. 4 Specifications of Required Main Parts
Parts
Specifications
Remarks
Auxiliary Relay (X1, X2)
Mini-Power Relay,
MY1F (or 2F) made
by OMRON
220/240V
Changeover Switch
(SS2, SS3)
Manual Switch
220/240V
3 Pin Connector Cord
PCC-1A
(connected to JST
connector, XARP -3)
five cords with
connectors as
one set
Low Volt.
0.3mm²
lower than 24V
Cord
(inside of
Unit)
220/240V
0.5~0.75mm²
Low Volt
0.5~0.75mm²
lower than 24V
Cord.
(outside of
Unit)
220/240V
2mm²
NOTES:
Make the wire to the terminals as short as possible.
Do not run the wires along high voltage cable. (crossing
is applicable.) If necessary to run wires along high
voltage cable, insert the low voltage cable(s) into metal
tube and ground it at one end. If sealed wires are used
at the low voltage wire side, ground it at one end of
shield wires. The maximum length should be 70m.
Indoor Unit PCB
3P Connector
(Cool)
(Heat)
SS3: Fixing Operation mode SW.
SS3: Changeover SW.
Control Circuit
Power
Source
(Cool)
(Heat)
Indoor Unit PCB
3P Connector
SS3: Snow sensor SW.
Control Circuit
Power
Source
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...