4
OPTIONAL FUNCTION
7
2. By pressing the push-switches PSW2 and PSW3,
input/output terminal name is changed. The following
shows the display changes when PSW2 and PSW3 are
pushed.
SEG2
SEG1
Indication for
Input 1
ú 1
ú 1
PSW2
PSW3
Indication for
Input 2
ú 2
ú 2
PSW2
PSW3
Indication for
Input 3
ú 3
ú 3
PSW2
PSW3
Indication for
Output 1
o 1
o 1
PSW2
PSW3
Indication for
Output 2
o 2
o 2
PSW2
PSW3
3. After the input/output terminal name is selected, select
your required function No. by pushing PSW2 or PSW3
while PSW1 is being pushed.
SEG2
SEG1
ú 2
2
*
*) This number is increased by 1 by pushing PSW2
while PSW1 is being pushed. This number is
decreased by 1 by pushing PSW3 while PSW1 is
being pushed.
4. After selecting the function No., return No. 1 pin at the
"OFF" side on the DSW8. The selected contents are
memorized in the outdoor unit printed circuit board. and
the function selection mode is stopped. The memorized
data is maintained even power source lines are
disconnected. The connecting details of each function
are described below, and the required parts are also
indicated below.
4.2.1.
DEMAND
In the case that the demand input terminals on the outdoor
unit printed circuit board are short-circuited, compressor(s)
is stopped. (In this case, the indoor unit(s) is put under
thermo-OFF condition.) The stoppage code No. "10" is
given. By disconnecting the demand switch contact,
restarting is available. The following indicates an example
for Demand at input 3 (between 1 and 2 pins of CN18).
Wiring Diagram Example of Demand Control
4.2.2.
FORCED STOPPAGE
The compressor is stopped and the indoor fan motor is
stopped when the forced stoppage input terminals(CN18
#1~ #2) on the outdoor unit PCB is short-circuited during
running. However, the remote control switch display
remains at the same mode and the stoppage cause code
"d1" will be No."10". In this case, if the input terminals are
opened, operation is resumed.
Wiring Diagram Example of Forced Stoppage:
Indoor Unit PCB
3P Connector
SS3: Demand SW.
Control Circuit
Power
Source
Indoor Unit PCB
3P Connector
SS3: Forced Stoppage SW.
Control Circuit
Power
Source
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...