4
6
OPTIONAL FUNCTION
n
Picking Up Cooling Operation Signal (RPK-FSGM is
not available)
This function is utilized to pick up the cooling operation
signal. The contact of RYa is closed when cooling
operation signal is ON despite "Thermo-ON" or "Thermo-
OFF". Connect the wires as shown below. The required
main parts are indicated in Table 4. 3
* Connector No.
Indoor Unit
CN5
RCD - FSG(E), RPF(I) - FSG(E)
CN20
RCI-FSGE, RPI-FSG(E), RPC-FSGE
n
Picking Up "Thermo-ON" Signal during Cooling
Operation (Only for RCD-FSG(E) and RPF(l)-FSG(E)
models)
This function is utilized to pick up the cooling "Thermo-ON"
signal of compressor running. Connect wires as shown
below. The required parts are indicated in Table 4. 3. The
contact of RYa is closed when "THERMOSTAT" is ON
during cooling operation mode.
NOTE:
"Thermo-ON" indicates that one of the micro-computer
control function "THERMOSTAT" is ON as a
thermostat.
4.2.
OUTDOOR UNIT
On the outdoor unit printed circuit board, there are three
input terminals to receive external signals and two output
terminals to send signals outwards. These signals are
available by setting as shown below.
Function No.
Input
Output
1
Fixing Heating Mode
Operation Signal
2
Fixing Cooling Mode
Alarm Signal
3
Demand
Compressor ON Signal
4
Snow Sensor
Defrosting Signal
5
Enforced Stoppage
--
Each input terminal and output terminal are set before
shipment as shown below.
Input/Output
Name
Connector Pin No.
Setting Function (No.)
Input 1
CN17 (1-2)
Fixed Heating Mode (1)
Input 2
CN17 (2-3)
Fixed Cooling Mode (2)
Input 3
CN18 (1-2)
Demand (3)
Output 1
CN16 (1-2)
Operation (1)
Output 2
CN16 (1-3)
Alarm (2)
In the case that the above setting change is required at
site, perform the following procedures.
1. Set No. 1 pin on the dip-switch, DSW8 on the outdoor
printed circuit board at the "ON" side while the main
power to the outdoor unit is being supplied. By setting,
function selection mode is available and the following
appears on the 7-segment display.
SEG2
SEG1
ú 1
1
Input/Output Terminal
Function No.
This display indicates that the function No. 1 (Fixed
Heating Mode) is set at input 1.
* Connector
PCB in Indoor Unit
Auxiliary Relay
3 Pin Connector Housing (JST-XHP-3)
CN5 Connector
PCB in Indoor Unit
Auxiliary Relay
3 Pin Connector Housing (JST-XHP-3)
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...