OPTIONAL FUNCTION
Operation During:
Cooling Operation:
Compressor is ON by closing terminals 2 and 3 at CN3
Compressor is OFF by opening terminals 2 and 3 at
CN3
Heating Operation:
Compressor is ON by closing terminals 1 and 2 at CN3
Compressor is OFF by opening terminals 1 and 2 at
CN3
Table 4. 2 Specifications on Required Components:
Component
Manufacturer or Specifications
Thermostat
Equivalent of YAMATAKE
R7031P005, R7031Q005
NOTES:
When a field-supplied room thermostat is used, select
the specified thermostat as below:
Contactor Load: DC24V 50 to 6 mA
Differential:
more than 1.5 degree
Do not use a thermostat utilizing mercury.
This function can be used together with 4.1.1 Remote
Control ON/OFF Funtion
4.1.5.
OPERATION CONTROL BY REMOTE
TEMPERATURE SENSOR
By using an optional remote temperature sensor, the
followings are available.
1. The unit is controlled by the average temperature of the
inlet air thermistor and remote temperature sensor.
2. In the case that the discharge air temperature exceeds
60 °C, the fan speed increases from "Medium" to "High"
or "Low" to "Medium".
Remote Temperature Sensor : THM-R2:
NOTES:
The remote temperature sensor can not be used
together with the remote control thermistor. (Refer to
the item 4.3.5 (10).)
During the heating operation, "Heating Temperature
Calibration" is automatically cancelled. (Refer to the
item 4.3.5 (1).)
4.1.6.
COOLING OR HEATING OPERATION
MODE SETTING CHANGE BY EXTERNAL
INPUT (Level Signal Input)
By utilizing this function, the cooling or heating operation
mode can be changed by giving a contact signal from the
outside to the unit. The operation mode is followed by the
field-supplied switch or the remote control switch, which is
used last.
Wiring Diagram Example of Remote Control 2:
Time Chart:
NOTE:
This function can not be used together with the
following functions; "Remote Control 2", "Remote
Control 3" and "Cancellation of Commands from
Remote Control Switch after Forced Stoppage".
Remote Sensor
Inlet Air Temperature
Thermistor
Remote Control
Switch
THM4
PCB
3P Connector
Indoor Unit PCB
Time
Control Circuit
Power
Source
COOL
HEAT
Signal to 1 & 2
of CN4
Control by R.C.S (Cool)
Heat
Cool
Control by R.C.S (Heat)
Heat
Cool
Operation mode
of Unit
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...