Checking of Compressor
CHECK LIST ON COMPRESSOR
Client:
Model:
Date:
Serial No:
Production Date:
Checker:
No.
Check Item
Check Method
Result
Remarks
1
Are THM8, THM9, THM12 and
THM13 correctly connected?
THM8, THM9, THM12, THM13:
Discharge Gas Thermistor
Are wires of each thermistor correctly
connected by viewing?
ó
Check to ensure that 7-segment indication of
Td1 is higher than Td2, Td3, Td4 when No.1
comp. is operating.
Td1: Temperature of THM8
Td2: Temperature of THM9
Td3: Temperature of THM12
Td4: Temperature of THM13
2
Are thermistors, THM8, THM9,
THM12 and THM13
disconnected?
Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
ó
Check to ensure that actually measured temp.
are greatly different from the indication (Td1,
Td2, Td3, Td4) during check mode.
3
Are connectors for current sensor
correctly connected
4
Is current sensor faulty?
5
Is current sensing part on PCB3
faulty?
Check to ensure that indication A1, A2, A3 and
A4 are 0 during compressor stopping.
ó
Check to ensure that indication A1, A2, A3 and
A4 are not 0 during compressor running.
(However, A2, A3 and A4 are 0 during stopping
of No.2, No.3 and No.4 comp.)
6
Is the direction of current
sensor(CTU, CTV) reverse?
Check the direction
by viewing.
7
Are power source wires, U and V
inserted correctly into current
sensor?
Check to ensure that wires are correctly inserted.
8
Are ex. valves (MV1 and MV2)
correctly connected?
Check to ensure that MV1
~
CN10 and MV2
~
CN11
are correctly connected.
9
Are ex. valve coils (MV1 and
MV2) correctly mounted?
Check to ensure that each coil is correctly mounted
on the valve.
10
Are the refrigeration cycle and
electrical wiring system
incorrectly connected?
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
11
Is opening of ex. valve
completely closed(locked)?
Check the following by the check mode of outdoor
unit.
Liquid Pipe Temp.(TL)<Air Intake Temp.(Ti)
during Cooling Operation
ó
Liquid Pipe Temp.(TL)>Air Intake Temp.(Ti)
during Heating Operation
12
Is opening of ex. valve fully
opened (locked)?
Check to ensure that liquid pipe temp. is lower than
air intake temp. of stopping indoor unit when other
indoor units are operating under cooling operation.
13
Are the contacts for comp.
magnetic switch CMC faulty?
Check the surface of each contact (L1, L2 and L3)
by viewing.
14
Is there any voltage abnormality
among L1-L2, L2-L3 and L3-L1?
Check to ensure that voltage imbalance is smaller
than 3%.
Please note that power source voltage must be
within 380V or 415V±10%, 220V±10 %.
15
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...