1
TROUBLESHOOTING
93
b. By touching the - side of the tester to the + terminal of
the diode module and the + side of tester to the ~
terminals (3 Nos.) of the diode module, measure the
resistance. If all the resistances are greater than 500 k
W
,
it is normal.
c. By touching the - side of the tester to the - terminal of the
diode module and the + side of tester to the
~
terminals
(3 Nos.) of the diode module, measure the resistance. If
all the resistances are from 5 to 50 k
W
, it is normal.
d. By touching the + side of the tester to the - terminal of
the diode module and the - side of tester to the
~
terminals (3 Nos.) of the diode module, measure the
resistance. If all the resistances are greater than 500 k
W
,
it is normal.
b)
c)
d)
n
Checking Method of Electronic Expansion Valve
Indoor Unit Electronic Expansion Valve
Outdoor Unit Electronic Expansion Valve
Locked with Fully Closed
Check for the liquid pipe temperature during
heating operation.
It is abnormal if the temperature does not
increase.
It is abnormal if the liquid pipe pressure does
not increase during cooling operation.
Locked with Slightly Open
It is abnormal if the liquid pipe pressure does
not increase and the outlet temperature of
the expansion valve decreases after the
cooling operation is started.
Locked with Fully Open
It is abnormal under the following conditions;
The temperature of freeze protection thermistor
becomes lower than the suction air temperature
when the unit under checking is stopped and
other units are under cooling operation.
It is abnormal under the following conditions;
After heating operation for more than 30
min., the discharge gas temperature of
compressor is not 10 °C higher than the
condensing temperature and there is no
other faults such as excessive charge of
refrigerant, etc.
Electronic expansion Valve
Freeze Protection
Thermistor
Unit under
checking
Other
units
Содержание FS3 Series
Страница 2: ......
Страница 4: ......
Страница 114: ......
Страница 190: ......
Страница 191: ...3 MAIN PARTS 19 3 8 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF OUTDOOR UNIT n Control Board 1 PCB1 1 2 ...
Страница 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Страница 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Страница 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Страница 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Страница 197: ...3 MAIN PARTS 25 3 10 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF REMOTE CONTROL SWITCH n PC 2H2 ...
Страница 198: ...3 26 MAIN PARTS n PC 5H ...
Страница 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Страница 200: ......
Страница 239: ......
Страница 240: ...SMGB0001 06 01 Printed in Spain ...