Replacing a Power Unit
7–7
Hitachi Unified Storage Hardware Service Guide
Replacing the Power Unit on a DBL/DBS Drive Box
To replace the Power Unit on a DBL/DBS Drive Box:
1. Confirm the status of the following LEDs:
- Red
ALM LED on the Power Unit to be replaced is ON.
- Green
RDY LED on the Power Unit not to be replaced is ON.
2. Hold up the latch on the Power Unit cable holder to release the lock, and
then slide the cable holder forward.
3. Disconnect the power cables connected to the Power Unit to be replaced.
You cannot remove the Power Unit with the power cable connected.
4. Wait at least 30 seconds before installing the new Power Unit.
5. Open the lever toward you (
?
) while pressing the latch on the Power Unit
inward with your thumb (
c
). When the lever is opened completely, the
Power Unit can be removed by pulling it forward.
6. Hold the Power Unit with both hands, then pull and remove it.
7. With the lever opened completely, insert the replacement Power Unit
into the slot. If you cannot insert the Power Unit into the slot easily,
adjust the position by returning the lever slightly, and then insert it.
8. Push the Power Unit all the way. Do not catch the SAS (ENC) Cable when
inserting the Power Unit.
9. Close the lever and tighten the Power Unit.
10.Connect the power cable.
11.Confirm the status of the following LEDs:
- Green
RDY LED on the Power Unit is ON.
- Green
READY LED on the front of the Controller Box is ON. This
LED may blink rapidly for up to 50 minutes.
- Red
ALARM LED and orange WARNING LED are OFF. If these two
LEDs blink slowly, visit the HDS Support Portal at
12.In Storage Navigator Modular 2, check the recovery after replacing
components (see
Checking recovery after replacing components on
).
NOTE: If the red ALM LEDs on the Power Unit of both controllers are ON,
visit the HDS Support Portal at
NOTE: If you do not wait at least 30 seconds, the Power Unit might not
recover normally. If you fail to wait at least 30 seconds and the Power Unit
does not recover, remove the Power Unit, wait at least 30 seconds, and
then reinstall it.
Содержание CBL
Страница 12: ...xii Hitachi Unified Storage Hardware Service Guide Serial Numbers Hitachi Unified Storage Models 110 and 130 ...
Страница 13: ...xiii Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS Either a or b is affixed ...
Страница 14: ...xiv Hitachi Unified Storage Hardware Service Guide Labels on the CBXSL Either a or b is affixed a b ...
Страница 15: ...xv Hitachi Unified Storage Hardware Service Guide Labels on the CBSS Either a or b is affixed a b ...
Страница 16: ...xvi Hitachi Unified Storage Hardware Service Guide Labels on the CBSL Either a or b is affixed a b ...
Страница 17: ...xvii Hitachi Unified Storage Hardware Service Guide Labels on the CBL CBLE CBLD Either a or b is affixed a b ...
Страница 18: ...xviii Hitachi Unified Storage Hardware Service Guide Labels on the DBS DBSD Either a or b is affixed a b ...
Страница 19: ...xix Hitachi Unified Storage Hardware Service Guide Labels on the DBL DBLD Either a or b is affixed a b ...
Страница 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Страница 21: ...xxi Hitachi Unified Storage Hardware Service Guide Labels on the DBF Either a or b is affixed a b ...
Страница 22: ...xxii Hitachi Unified Storage Hardware Service Guide Labels on the DBX Either a or b is affixed kg a b a b ...
Страница 23: ...xxiii Hitachi Unified Storage Hardware Service Guide Labels on front of the DBW added on April 2014 ...
Страница 25: ...xxv Hitachi Unified Storage Hardware Service Guide Labels on rear of the DBW added on April 2014 ...
Страница 28: ...xxviii Hitachi Unified Storage Hardware Service Guide DBX DBW Labels on cache backup battery CBL CBLE CBLD ...
Страница 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Страница 35: ...xxxv Hitachi Unified Storage Hardware Service Guide Labels on Management Module CBL CBLE CBLD LAN UPS ...
Страница 36: ...xxxvi Hitachi Unified Storage Hardware Service Guide Labels on I O Module ENC DBS DBSD DBL DBLD DBF ...
Страница 37: ...xxxvii Hitachi Unified Storage Hardware Service Guide DBW Labels on I O Card ENC DBX Labels on Host Connector ...
Страница 38: ...xxxviii Hitachi Unified Storage Hardware Service Guide Labels on SAS ENC Cable Labels on cable holder DBX In ...
Страница 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Страница 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Страница 126: ...3 8 Procedures before and after replacing components Hitachi Unified Storage Hardware Service Guide ...
Страница 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Страница 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Страница 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Страница 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Страница 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Страница 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Страница 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Страница 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Страница 286: ...Glossary 12 Hitachi Unified Storage Hardware Service Guide A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ...
Страница 290: ...Index 4 Hitachi Unified Storage Hardware Service Guide U Upgrading Hitachi Unified Storage 130 15 1 ...
Страница 291: ...1 Hitachi Unified Storage Hardware Service Guide ...