3. Servicing
Electrical components
SMGB0097 rev.0 - 07/2015
84
3.4.9
Contactors (CMC, CMCD, CMCS)
C A U T I O N
In RCME-WH units, contactors are used for the delta start automation. Take note where each cable is connected in order
to avoid any mistake when reassembling. An incorrect connection may result in a compressor damage.
To proceed to the removal of contactors, follow the steps described below.
1
Remove all the wiring with a Phillips screwdriver.
2
Remove the screws that fixes the contactors to the plate.
3
When reassembling, proceed in reverse order than
removing.
Screws
Use a Phillips screwdriver to remove the screws. 2 screws at the top and
1 screw at the bottom.
3.4.10
Fuses (EF1, EF2, EF3. EFR, EFS, EFT)
“EF” fuse series are mounted on DIN rail. To replace any damaged fuse proceed as described below.
1
Once the damaged fuse is detected, simply push the holder down. The damaged fuse appears. Pull it and proceed to
its replacement