Figure 9 APAC and EMEA PDU for the Hitachi Universal V2B Rack (Three-phase
3P16A-15C13-3C19CE.P)
Part
number
Region
Quantity
Power input
per PDU
Power
output per
PDU
Total rack
amperage
available
3P16A-15C
13-3C19CE.
P
APAC and
EMEA
4/rack
2/side
Three phase
400V max. 16A
(12.8A rated)
50Hz / 60Hz
Delta/wYe: wYe
IEC309 3P + N
+ E input
power plug
4.5 m (14.76
feet) cable
15 IEC C13
+ 3 IEC C19
sockets
Max
allowable
current:
38.4A
8.8kVA
77A (17.6kVA)
APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P
The following figure and table describe the specifications of the PDU.
APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform G900 Hardware Reference Guide
117