3. General data
TCGB0075 rev.0 - 11/2012
57
3
3.2 Outdoor unit
3.2.1 RAS-(4-6)HVRNME-AF
Model
RAS-4HVRNME-AF
RAS-5HVRNME-AF
RAS-6HVRNME-AF
Electrical power supply
1~ 230V 50Hz
Color (Munsell code)
-
Natural gray (1.0Y8.5/0.5)
Sound pressure level
dB(A)
46
48
50
Sound power level
dB(A)
65
67
69
Outside mea-
surements
Height
mm
1,380
1,380
1,380
Width
mm
950
950
950
Depth
mm
370
370
370
Net weight
kg
103
104
104
Refrigerant
-
R-410A
Flow control
-
Microprocessor-controlled expansion valve
Compressor
-
DC inverter driven
Quantity
-
1
1
1
Power
kW
1.80
2.50
2.50
Heat exchanger
-
Multi-pass cross-finned tube
Outdoor fan
-
Propeller fan
Quantity
-
2
2
2
Air flow rate
m³/min
80
90
100
Power
W
70+70
70+70
70+70
Refrigerant pipe connection
-
Flare-nut connection (factory supplied)
Size
Liquid piping
mm
(in)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Gas piping
mm
(in)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Refrigerant charge
kg
3.90
4.00
4.00
Maximum current
A
18.0
23.0
23.0
Packaging measurements
m³
0.70
0.70
0.70
N O T E
The sound pressure level is based on following conditions:
• 1 meter from the frontal surface of the unit; 1.5 meters from floor level.
•
Voltage of the power source is 230V.
The above data is measured in an anechoic chamber, so reflected sound should be taken into consideration
when installing the unit.
Содержание 7E300020
Страница 2: ......
Страница 4: ......
Страница 18: ......
Страница 54: ......
Страница 83: ...6 Working range TCGB0075 rev 0 11 2012 83 6 6 Working range Index 6 1 Working range 84 ...
Страница 94: ......
Страница 134: ......
Страница 146: ......
Страница 150: ......
Страница 156: ......
Страница 157: ......