Installation EAGLE20/30
Release 12 03/2021
39
2.6
Operating the device
Note:
Relevant for North America:
The torque for tightening the supply voltage terminal block on the device is
4.5 lb-in (0.51 Nm).
The torque for tightening the signal contact and input terminal block on the
device is 3 lb-in (0.34 Nm).
Use screws to secure the connectors to the device.
Enable the supply voltage.
2.7
Connecting data cables
2.7.1
Twisted Pair ports
Note the following general recommendations for data cable connections in
environments with high electrical interference levels:
Keep the length of the data cables as short as possible.
Use optical data cables for the data transmission between the buildings.
When using copper cables, provide a sufficient separation between the
power supply cables and the data cables. Ideally, install the cables in
separate cable channels.
Verify that power supply cables and data cables do not run parallel over
longer distances. To reduce inductive coupling, verify that the power
supply cables and data cables cross at a 90° angle.
Use shielded data cables for gigabit transmission via copper cables, for
example SF/UTP cables according to ISO/IEC 11801. Exclusively use
shielded data cables to meet EMC requirements according to EN 50121-
4 and marine applications.
Connect the data cables according to your requirements.
See “Ethernet ports” on page 25.
WARNING
ELECTRIC SHOCK
Before connecting the electrical wires,
always
verify that the requirements
listed are complied with.
See “Requirements for connecting electrical wires” on page 9.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.