Items
Article
Method
Condition to verify
Criterion
Slow-down OFF
Output Adj. Dial
Max.
556+/-25V
Slow-down OFF
Output Adj. Dial
Min
421+/-20V
Optional
Tester
Output Adj. Dial
Terminals: U-V,
V-W, W-U
480+/-3V
V
480+/-6V
No Load
Hz
Meter
attached
Ditto
63+/-1Hz
A
Ditto
14.4+/-0.5A
V
482+/-6V
G
e
n
e
ra
ti
n
g
O
u
tp
u
t
C
h
e
c
k
6
0
H
z
Si
n
g
le
3-Phase
480V
Loaded
min
-1
Optional
Tester
3740+/-50 min
-1
No Load
V
240+/-1V
A
18.0+/-0.5A
Si
n
g
le
1-Phase
240V
Loaded
V
Optional
Tester
Output Adj. Dial
Terminals: T-R
248+/-6V
No Load
V
120+/-1V
A
18.0+/-0.5A
Si
n
g
le
Loaded
V
Output Adj. Dial
Terminals: R-N
120+/-3V
1-Phase
120V
No Load
V
68+/-3V
A
18.0+/-0.5A
Ec
o
Loaded
V
Output Adj. Dial
Terminals: N-T
120+/-3V
No Load
V
120+/-3V
A
18.0+/-0.5A
6
0
H
z
Si
n
g
le
Loaded
V
Optional
Tester
Single Receptacle
120+/-3V
Loaded
Run at regular speed
G
e
n
e
ra
ti
n
g
O
u
tp
u
t
C
h
e
c
k
Slow-down Feature
Slow-down
ON
Load Cut
Return to Slow-down
in 8+/-2 second
1: Adjust the value by Power Controller VR2, finding it out of the required value range.
Spray screw lock bond (Recommendation - Three Bond No.1401C, Red) after adjusting.
Refer to “6.5 Power Controller”.