![Hioki PW3390 Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/hioki/pw3390/pw3390_instruction-manual_2137353074.webp)
PW3390 Power Analyzer Communication Command Instruction Manual Second Edition
74/107
Set and Query Communication Output Items of Motor Input
Syntax
Command
:MEASure:ITEM:EXTernalin <0 to 255>
Query
:MEASure:ITEM:EXTernalin?
Response
128
64
32
16
8
4
2
1
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
-
-
-
-
SLIP
PM
EXTB
EXTA
Description
Command
Sets the communication output item of the motor input as 0
–
255.
Query
Returns the setting for the communication output item of the motor input as 0
– 255.
Example
Command
:MEAS:ITEM:EXT 7
Set the EXTA, EXTB, PM of the motor analysis function calculation value to
ON.
Query
:MEAS:ITEM:EXT?
Response
:MEASURE:ITEM:EXTERNALIN 7 (WHEN HEADER IS ON)
7 (WHEN HEADER IS OFF)
Initialize Harmonic Communication Output Data Items
Syntax
Command
:MEASure:ITEM:HARMonic:ALLClear
Description
Command
Initializes the Harmonic communication output data item.
All Harmonic communication output data item set to OFF.
Example
Command
:MEAS:ITEM:HARM:ALLC
Initialize the Harmonic communication output data item.
Содержание PW3390