13.2 Input Specifications/Output Specifications/Measurement Specifications
194
-1. Basic specifications
13.2 Input Specifications/Output Specifications/
Measurement Specifications
Number of channels
Voltage: 4 channels
Current: 4 channels
Input terminal form
Voltage: Plug-in terminals (Safety terminals)
Current: Dedicated connectors (Hioki PL14)
Current sensor power supply
For AC/DC auto-zero current sensors and AC flexible current sensors
+5 V
±
0.25 V, -5 V
±
0.25 V; supplied current: 30 mA max./ch.
Measurement line type
Single-phase 2-wire: 1P2W
Single-phase 3-wire: 1P3W
3-phase 3-wire 2-watt meter measurement: 3P3W2M
3-phase 3-wire 3-watt meter measurement: 3P3W3M
3-phase 4-wire: 3P4W
3-phase 4-wire 2.5 element: 3P4W2.5E
In addition to one of the above, input CH4.
(must be synchronized to reference channel during AC/DC measurement)
Input methods
Voltage input section: Isolated and differential inputs
(Between U1,U2 and U3: channels not isolated, Between U1,U2 and U3 to U4: channels isolated)
Current input section: Isolated input through a current sensor
Input resistance
Voltage input section: 4 M
Ω ±
2%
Current input section: 100 k
Ω
±
10%
Maximum input voltage
Voltage input section: 1000 V AC, ±600 V DC, 6000 V peak
Current input section: 1.7 V AC/DC, 2.4 V peak
Maximum rated voltage to earth
Voltage input section: 600 V AC (Measurement categories IV), anticipated transient overvoltage 8000 V
Current input section: Depends upon the current sensor being used
Measurement method
Digital simultaneous sampling of voltage and current, zero-cross synchronized calculation method
Sampling frequency
Voltage and current, active power, etc.
: 200 kHz
Transient voltage measurement
: 2 MHz
A/D converter resolution
RMS voltage and current: 16bit
Transient voltage measurement: 12bit
Display range
Voltage: 0.48 V to 780 V
Current: 0.5% to 130% of range
Power: 0.0% to 130% of range
Measurement items other than the above: 0% to 130% of range
Zero display range
Voltage: Less than 0.48 V; when the voltage RMS value is 0, the power value is set to 0.
Current: Less than 0.5% f.s.; when the voltage RMS value is 0, the power value is set to 0.
Effective measurement
range
Voltage: 10 V AC to 780 V AC, 1 V DC to 600 V DC
Current: 1% to 120% of range
Power: 0.15% to 130% of range (with both voltage and current within effective measuring range)
See separate specifications for harmonic measurement
Effective peak range
Voltage measurement:
±
1200 V
Transient voltage measurement:
±
6.0000 kV
Current measurement:
±
400% of range
HIOKI PQ3198A961-03
Содержание PQ3198
Страница 2: ...HIOKI PQ3198A961 03...
Страница 6: ...Contents iv HIOKI PQ3198A961 03...
Страница 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Страница 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Страница 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Страница 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Страница 116: ...6 4 Displaying Harmonics 110 Holding the display Hold Measured values and waveforms will be held HIOKI PQ3198A961 03...
Страница 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Страница 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Страница 296: ...A32 HIOKI PQ3198A961 03...
Страница 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Страница 300: ...Index Index 4 HIOKI PQ3198A961 03...
Страница 301: ...HIOKI PQ3198A961 03...
Страница 302: ...HIOKI PQ3198A961 03...
Страница 303: ...HIOKI PQ3198A961 03...
Страница 304: ...www hioki com HIOKI PQ3198A961 03...