3280-10

CLAMP ON HiTESTER

INSTRUCTION MANUAL

November 2006 Revised edition 12 Printed in Japan

3280C980-12 06-11H

Introduction

Inspection

Safety

DANGER

This instrument is designed to conform to IEC 61010 Safety Standards, and has been

thoroughly tested for safety prior to shipment. However, mishandling during use could

result in injury or death, as well as damage to the instrument. Be certain that you

understand the instructions and precautions in the manual before use. We disclaim

any responsibility for accidents or injuries not resulting directly from instrument defects.

Safety Symbols

The

symbol printed on the instrument indicates that the user should

refer to a corresponding topic in the manual (marked with the

symbol)

before using the relevant function.

In the manual, the

symbol indicates particularly important information

that the user should read before using the instrument.
Indicates a double-insulated device.
Indicates DC (Direct Current).
Indicates AC (Alternating Current).
Indicates both DC (Direct Current) and AC (Alternating Current).
Indicates a grounding terminal.
Indicates that the instrument may be connected to or disconnected from

a live circuit

DANGER

Indicates that incorrect operation presents an extreme hazard that

could result in serious injury or death to the user.

WARNING

Indicates that incorrect operation presents a significant hazard that

could result in serious injury or death to the user.

CAUTION

Indicates that incorrect operation presents a possibility of injury to

the user or damage to the instrument.

NOTE

Indicates advisory items related to performance or correct

operation of the instrument.

Notes on Operation

WARNING

During current measurement, to avoid an electric shock accident, do not connect the

test leads to the instrument.

To avoid electric shock, do not allow the instrument to get wet, and do not use it

when your hands are wet.

Do not attempt to adjust or repair the instrument with the case open and with

voltage being input. Such adjustments or repairs should only be made by a

technician who fully understands the dangers involved.

To avoid electric shock when measuring live lines, wear appropriate protective gear,

such as insulated rubber gloves, boots and a safety helmet.

CAUTION

Do not store or use the instrument where it could be exposed to direct sunlight, high

temperature or humidity, or condensation. Under such conditions, the instrument may

be damaged and insulation may deteriorate so that it no longer meets specifications.

Accuracy

Function

Range

Accuracy*

Max. input

current

ACA

(

A)

42.00 A

420.0 A

1000 A

1.5% rdg.

5 dgt.

(Frequency range 50 - 60 Hz)

2000 A rms

continuous

Effect of conductor position:

5.0% (in any direction from sensor center)

Maximum rated voltage to earth: CAT III 600 V (Current measurement section)

Function

Range

Accuracy*

Input impedance

Max. input

voltage

ACV

(

V)

4.200 V

42.00 V

420.0 V

600 V

2.3% rdg. 8 dgt.

(Frequency range

50 - 500 Hz)

 11 M

5%

 10 M

5%

 10 M

5%

 10 M

5%

600 V rms

DCV

(

V)

420.0 mV

4.200 V

42.00 V

420.0 V

600 V

1.3% rdg.

4 dgt.

 100 M

or over

 11 M

5%

 10 M

5%

 10 M

5%

 10 M

5%

600 V DC

Maximum rated voltage to earth: CAT III 300 V, CAT II 600 V (Voltage measurement
section)

Function

Range

Accuracy*

Open terminal voltage

Overload

protection

Resistance

[

Ω]

420.0

4.200 k

42.00 k

420.0 k

4.200 M

42.00 M

2.0% rdg.

4 dgt.

2.0% rdg.

4 dgt.

2.0% rdg.

4 dgt.

2.0% rdg.

4 dgt.

5.0% rdg.

4 dgt.

10.0% rdg.

4 dgt.

 3.4 V or less

 0.7 V (typ.) 3.4 V or less

 0.47 V (typ.) 3.4 V or less

 0.47 V (typ.) 3.4 V or less

 0.47 V (typ.) 3.4 V or less

 0.47 V (typ.) 3.4 V or less

250 V rms

Continuity

[

]

420.0

2.0% rdg.

6 dgt.

(Threshold level

50

30

  )

 3.4 V or less

250 V rms

Specification

LCD panel

4199 maximum display value

Out of range indication

OF or -OF

Battery low warning
Data hold indication
Zero suppression

5 count or less (current measurement only)

Display update rate

FAST

400 ms 25 ms

SLOW

3.2 s 0.2 s

Range switching

Auto range / Manual range

Withstand voltage

3536 VrmsAC sine wave (for 15 seconds ) between case and circuit

5312 VrmsAC sine wave (for 15 seconds ) between clamp sensor and case

5312 VrmsAC sine wave (for 15 seconds ) between clamp sensor and circuit

Location for use

Altitude up to 2000 m (6562 feet), indoors

Maximum conductor

diameter for measurement

φ

33 mm (1.30") or less

Temperature and humidity

for guaranteed accuracy

0 to 40

(32

to 104 ), 80%RH max (no condensation)

Guaranteed accuracy period 1 year, or opening and closing of the Clamp sensor 10,000 times,

whichever comes first

Operating temperature and

humidity

0 to 40

(32

to 104 ), 80%RH max (no condensation)

Storage temperature

-10 to 50

(14

to 122 ) (no condensation)

Temperature characteristics In 0 to 40

(32

to 104 ) range: 0.1 x Measurement accuracy /

( )

Power supply

Rated supply voltage 3 V DC x 1

CR2032 x 1 Lithium battery

Maximum rated power

15 mVA

Continuous operating time

Approx. 150 hours (standard), Approx. 80 hours min. (in AC current

measurement mode, continuous, no load)

Dimensions and mass

Approx. 57W x 175H x 16D mm, approx. 100 g

(Approx. 2.24"W x 6.89"H x 0.63"D, approx. 3.5 oz.)

Drop proof

One meter to concrete

Accessories

Instruction Manual, 9398 CARRYING CASE, 9208 TEST LEADS

Options

9209 TEST LEADS HOLDER

Applicable standards Safety:

 EMC:

EN61010

Current measurement section: Measurement category CAT III 600 V,

Pollution Degree 2 (anticipated transient overvoltage 6000 V)

Voltage measurement section: Measurement Category CAT III 300 V, CAT II

600 V, Pollution Degree 2 (anticipated transient overvoltage 4000 V)

UL61010B

CAN/CSA-C22.2No. 1010

EN61326

Functions and Display

Names and Functions of Parts

Connect

the test

leads to

the object

to be

measured.

10.

9.

Display:

Measurement

value

Units

Symbols

Decimal point

1.

4.

5.

6.

Battery cover (rear)

2.

3.

3.

7.

8.

Measurement Procedures

DANGER

Observe the following precautions to avoid electric shock.

Always verify the appropriate setting of the function selector before connecting the

test leads. Disconnect the test leads from the measurement object before switching

the function selector.

Never apply voltage to test leads when the Resistance, Continuity Check functions

are selected. Doing so may damage the instrument and result in personal injury. To

avoid electrical accidents, remove power from the circuit before measuring.

Test leads and this instrument should only be connected to the secondary side of a

breaker, so the breaker can prevent an accident if a short circuit occurs.

Connections should never be made to the primary side of a breaker, because

unrestricted current flow could cause a serious accident if a short circuit occurs.

AC Current Measurement (

A )

DANGER

To avoid short circuits and potentially life-threatening hazards, never attach the

instrument in current measurement mode to a circuit that operates at more than the

maximum rated voltage to earth CAT III 600 V.

No

OK

2.

1.

Voltage Measurement

DANGER

The maximum input voltage is 600 V AC/DC. Attempting to measure voltage in

excess of the maximum input could destroy the instrument and result in personal

injury or death.

To avoid electrical shock, be careful to avoid shorting live lines with the test leads.
In voltage measurement mode, the maximum rated voltage between input terminals

and ground is CAT III 300 V, CAT II 600 V. Attempting to measure voltages

exceeding 600 V with respect to ground could damage the instrument and result in

personal injury.

Test leads

1.

Outlet

3.

2.

Black (-)

test lead

Battery

Red (+)

test lead

1.

2.

3.

Resistance Measurement (

)

Test

leads

Resistor

1.

2.

3.

Continuity Test (

)

Test

leads

1.

3.

Cord

2.

Maintenance

CAUTION

If the protective functions of the instrument are damaged, either remove it from

service or mark it clearly so that others do not use it inadvertently.
To clean the instrument, wipe it gently with a soft cloth moistened with water or mild

detergent. Never use solvents such as benzene, alcohol, acetone, ether, ketones,

thinners or gasoline, as they can deform and discolor the case.
To avoid corrosion from battery leakage, remove the batteries from the instrument if

it is to be stored for a long time.
If the instrument seems to be malfunctioning, confirm that the battery is not

discharged, and that the test leads are not open circuited before contacting your

dealer or Hioki representative. Pack the instrument carefully so that it will not be

damaged during shipment, and include a detailed written description of the problem.

Hioki cannot be responsible for damage that occurs during shipment.

Replacing Battery

WARNING

If the instrument is connected to a line that is to be measured, dangerous voltage

levels may be applied to the terminals, and removing the case may expose live

components.

To avoid electric shock when replacing the battery, first disconnect the test leads

from the object being measured. Also, after replacing the battery, always replace the

cover and tighten the screw before using the instrument.

Use only CR2032 (Panasonic or MAXELL) lithium battery. Use of any other battery

may result in explosion.

When replacing the battery, be sure to insert them with the correct polarity.

Otherwise, poor performance or damage from battery leakage could result.

Battery may explode if mistreated. Do not short-circuit, recharge, disassemble or

dispose of in fire. Handle and dispose of batteries in accordance with local

regulations.

Keep batteries away from children to prevent accidental swallowing.

Battery cover

Battery

Using the 9209 TEST LEADS HOLDER (Option)

HEAD OFFICE

81 Koizumi, Ueda, Nagano 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
E-mail: [email protected]

HIOKI USA CORPORATION

6 Corporate Drive, Cranbury, NJ 08512, USA
TEL +1-609-409-9109 / FAX +1-609-409-9108

URL:http://www.hioki.co.jp

1.

2.

Thank you for purchasing the HIOKI 3280-10 CLAMP ON HiTESTER.

To obtain maximum performance from the instrument, please read this manual first, and

keep it handy for future reference.

When you receive the instrument, inspect it carefully to ensure that no damage occurred

during shipping. If damage is evident, or if it fails to operate according to the

specifications, contact your dealer or Hioki representative.

Measurement categories (Overvoltage categories)

The current measurement section conforms to CAT III 600 V safety requirements, and the
voltage measurement section conforms to CAT III 300 V, CAT II 600V requirements.
To ensure safe operation of measurement instruments, IEC 61010 establishes safety
standards for various electrical environments, categorized as CAT I to CAT IV, and called
measurement categories. These are defined as follows.
CAT I : Secondary electrical circuits connected to an AC electrical outlet through a

transformer or similar device.

CAT II : Primary electrical circuits in equipment connected to an AC electrical outlet by a

power cord (portable tools, household appliances, etc.)

CAT III : Primary electrical circuits of heavy equipment (fixed installations) connected directly

to the distribution panel, and feeders from the distribution panel to outlets.

CAT IV : The circuit from the service drop to the service entrance, and to the power meter

and primary overcurrent protection device (distribution panel).

Higher-numbered categories correspond to electrical
environments with greater momentary energy, so a
measurement instrument designed for CAT III
environments can endure greater momentary energy
than one designed for CAT II. Using a measurement
instrument in an environment designated with a higher-
numbered category than that for which the instrument is
rated could result in a severe accident, and must be
carefully avoided.
Never use a CAT I measuring instrument in CAT II, III, or IV environments.
The measurement categories comply with the Overvoltage Categories of the IEC60664 Standards.

This manual contains information and warnings essential for safe operation of the

instrument and for maintaining it in safe operating condition. Before using the

instrument, be sure to carefully read the following safety notes.

The following symbols in this manual indicate the relative importance of cautions and

warnings.

Follow these precautions to ensure safe operation and to obtain the full benefits of the various functions.

23

5

(73

9 ), 80%RH or less, no condensation.

Accuracy is guaranteed for input falling within 10% to 100% of each respective range.

AC measurement: mean value measurement

*: rdg. (reading or displayed value), dgt. (resolution)

Auto Power Save Function

This function automatically switches to the power save state when 30 minutes have

elapsed since the last operation.

The auto power save function is activated automatically when the power is turned on.

To restore from the auto power save state, turn the function switch to the OFF

position once.

NOTE

:

The auto power save function cannot be canceled.

Auto-range Function

When measuring an AC current (

A), AC voltage (

V), DC voltage (

V), or resistance

(

), the measurement range is automatically set to the most appropriate range.

Manual Range Function

Power on the tester while holding down a key to select a manual range for measuring

AC current (

A) , AC voltage (

V) , DC voltage (

V) or resistance (

). Note that this

function is not available for continuity testing. Press the

SAMP. F/S key to step

to the next range.

Powering on with the HOLD key held down: manual ranging, with FAST display update

Powering on with the

SAMP. F/S key held down: manual ranging, with SLOW

display update

Overflow indication

When the input exceeds the measurement range, "OF" or "-OF" is displayed.

1. Display

2. Clamp sensor

3. Operation grip

4. Function switch

OFF / AC current ( A) / AC voltage

( V) / DC voltage ( V) / Resistance

and Continuity check (

/

)

5.

SAMP. F/S key

Measuring AC current or AC or DC

voltage

Switches display update rate

(FAST/SLOW).

If the display value is fluctuating and

hard to read, switch to the slow

update (SLOW: approximately every

3 seconds) to stabilize the display.

Measuring resistance or continuity

Switches between resistance

measurement (

) and continuity

testing (

).

6. HOLD key

Press this to hold the display value

(the

indication appears). Press

once more to cancel the hold

function.

7. Connector 8. Plug

Connect the test lead plug to the connector for voltage measurement, resistance

measurement, or continuity testing. Align the slot on the plug with the key in the

connector.

9. Red test lead (+) 10. Black test lead (-)

Pre-Operation Inspection (Check the following before using the

instrument.)

The cladding of the test lead shall not be torn, and the metal shall not be exposed. (If

damage has occurred, replace with the specified test lead [Model 9208]. Failure to do

so may result in electric shock.)
The clamp sensor or the case shall be free of damage. (If damage has occurred,

avoid using the instrument. Use of the instrument under these conditions may result in

electric shock.)
The mating portions of the clamp sensor shall mate properly. The mating portions of

the clamp sensor should also be free of any scratches or cracks.
Battery power should be near full capacity when power is turned on. (If the battery is

near exhaustion, the indicator "

" will light up. Using a battery close to exhaustion

may result in incorrect measurements.)
The reading should be around 0 A using the current function when no measurements

are being made.
The reading should be around 0 V using the voltage function while short-circuiting the

test lead.
The reading should be around 0

using the resistance function while short-circuiting

the test leads.

NOTE:

Please note that waveforms that include elements outside the frequency

characteristic range may not be measured correctly.

Accurate measurement may be impossible in the presence of strong magnetic

fields, such as near transformers and high-current conductors, or in the

presence of strong electromagnetic fields such as near radio transmitters.

1. Set the function switch to

A.

2. Clamp the tester on the conductor, so

that the conductor passes through the

center of the clamp core. Clamp the

tester on one lead only.

Check that the test lead plug is firmly connected to the tester before beginning

measurement.

Measuring AC Voltage  (

V )

Plug the test leads into the connector.

1. Set the function switch to

V.

2. Connect the test leads to the object to be

measured. When measuring AC voltage,

the polarity of the leads can be ignored.

3. Read the display.

Measuring DC Voltage (

V )

Plug the test leads into the connector.

1. Set the function switch to

V.

2. Connect the test leads to the object to be

measured.

3. Read the display.

NOTE

:

Reversing the polarity of the leads

displays a negative value.

Plug the test leads into the connector.

1. Set the function switch to

/

.

2. Connect the test leads to the object to be

measured.

3. Read the display.

Plug the test leads into the connector.

1. Set the function switch to

/

.

2. Press the

key, so that the

indication appears.

3. Connect the test leads to the object to be

measured.

Conductivity is good when the buzzer

sounds.

NOTE

:

When the battery is exhausted, the

indication

appears in the display.

1. Remove the test leads from the test item, and power the

instrument off.

2. Remove the instrument from the case, and remove the

screws on the battery cover.

3. Remove the used battery.

4. Being careful about the polarity, insert the new battery of

the specified type. (CR2032 lithium battery:Panasonic or

MAXELL)

5. Replace the battery cover and fasten the screws.

NOTE

:

The battery included with this instrument was

inserted for TESTING PURPOSES ONLY. Battery life will vary. Please replace

the original battery with a new battery as soon as it is depleted.

CR2032 lithium batteries (Panasonic or MAXELL) can be purchased at

electronics and appliance stores where specialized batteries are sold.

1. Remove the battery cover, and in its place fit the test lead holder (option). Fasten the

screws securely.

2. Insert the test lead into the test lead holder.