4.4 Setting Event Detection [REC&EVENT]
71
4
A voltage swell, voltage dip or interruption of the nominal voltage is recorded
as an event.
See:
"Voltage Swell" (p. 110), "Voltage Dip" (p. 111), "Interruption" (p. 111)
Setting Voltage Swell, Dip and Interruption Events
Move to the setting item.
Select the screen.
1
2
Setting Contents
Voltage Swell
Set a percentage larger than the nominal line voltage (default 110%).
Voltage Dip
Set a percentage smaller than the nominal line voltage (default 90%).
Interruption
Set a percentage smaller than the nominal line voltage (default 10%).
Change a numerical value
([
]: increase the value, [
]:
decrease the value)
3
Accept
Cancel
In all cases, an event is recorded when the threshold is breached in either direction (once
upon onset, and once again upon recovery).
Upon event recovery ("event out "), the continuous period and worst-case voltage swell val-
ues are displayed.
Upon event onset ("event in "), an event voltage fluctuation graph is recorded.
What is Voltage Swell?
Voltage swell is a rise of rms voltage, where a threshold is set above the nominal voltage.
When the rms voltage rises above the threshold, it is detected as an "event in (onset)" voltage swell
event. Subsequently, when the voltage falls back below the threshold (minus appropriate hystere-
sis), it is detected as an "event out (recovery)" voltage swell event.
What is Voltage Dip?
Voltage dip is the opposite of voltage swell, that is a fall of rms voltage where a threshold is set
below the nominal voltage.
When the rms voltage falls below the threshold, it is detected as an "event in (onset)" voltage dip
event. Subsequently, when the voltage rises back above the threshold (plus appropriate hystere-
sis), it is detected as an "event out (recovery)" voltage dip event.
What is Interruption?
This is the power suspension state when voltage drops to a threshold below the nominal voltage
and further below the voltage dip threshold.
When the rms voltage falls below the threshold, it is detected as an "event in (onset)" voltage in-
terruption event. Subsequently, when the voltage rises back above the threshold (plus appropriate
hysteresis), it is detected as an "event out (recovery)" voltage interruption event.
Содержание 3197
Страница 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Страница 2: ......
Страница 8: ...Contents vi ...
Страница 30: ...1 3 Measurement Flowchart 22 ...
Страница 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Страница 86: ...4 6 Initializing the Instrument System Reset 78 ...
Страница 117: ...6 3 Viewing Anomalous Phenomena EVENT screen 109 6 Viewing the INRUSH Screen DETAILS WAVEFORM INRUSH ...
Страница 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Страница 139: ...7 2 Installing JRE 131 7 5 When the installation process has completed successfully click Finish Click ...
Страница 176: ...9 4 Disposing of the Instrument 168 ...
Страница 199: ......
Страница 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...