![Hioki 3197 Скачать руководство пользователя страница 123](http://html.mh-extra.com/html/hioki/3197/3197_instruction-manual_2137178123.webp)
6.3 Viewing Anomalous Phenomena (EVENT screen)
115
6
Recordable Number of Events
The number of events that can be recorded is as follows regardless of whether internal memory is
partitioned.
Event
Recordable
Qty.
Description
Event data
Total 50
Overall Event List, details, voltage/current wave-
forms
Event voltage fluctuation graph
data
Total 20
Event voltage fluctuation graph for 3 seconds (*U)
Inrush current fluctuation graph
data
1
Inrush current fluctuation graph for 30 seconds (*I)
The number of recorded events is indicated on the upper
part of the screen.
Events recorded in internal memory are represented by
colored blocks.
A total of 50 blocks can be colored, beginning at the bot-
tom left and ending at the top right.
Indicates that six events have been recorded
Indicates that 46 events have been recorded
Although up to 50 inrush events can be detected, inrush current fluctua-
tion data can be recorded (and a graph displayed) for only one INRUSH
event (indicated by *I in the Event List).
Event Monitor
The number of occurrences of each event type is displayed. Event types that have not occurred are
indicated by "0". When an event occurs, the number of occurrences is displayed in red.
Item
Description
Event Type
Tran.
Transient Overvoltage
Swell
Voltage Swell*
Dip
Voltage Dip*
Inter.
Interruption*
Ext.
External (Start, Stop, Timer, Manual or Inrush current)
* Voltage swell, voltage dip and interruption events have EVENT IN (onset) and EVENT OUT (re-
covery) occurrences. Therefore, most such events occur in pairs (onset and recovery), and the
monitored values are usually multiples of two.
Содержание 3197
Страница 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Страница 2: ......
Страница 8: ...Contents vi ...
Страница 30: ...1 3 Measurement Flowchart 22 ...
Страница 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Страница 86: ...4 6 Initializing the Instrument System Reset 78 ...
Страница 117: ...6 3 Viewing Anomalous Phenomena EVENT screen 109 6 Viewing the INRUSH Screen DETAILS WAVEFORM INRUSH ...
Страница 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Страница 139: ...7 2 Installing JRE 131 7 5 When the installation process has completed successfully click Finish Click ...
Страница 176: ...9 4 Disposing of the Instrument 168 ...
Страница 199: ......
Страница 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...