4.6. Making DC Output Connections
Making DC Output Connections
Installer is responsible to provide suitable dc output, battery, and dc load wiring.
Guidelines for DC Connections
Guidelines for DC Connections
1. Size the dc wiring to minimize voltage drop. Acceptable wire size depends on the
installation. As a guideline, voltage drop should not exceed 1% of nominal output voltage
at full current. Refer to the following table to determine the voltage drops for various wire
sizes, currents and distances.
W
Wir
ire Sizing Chart
e Sizing Chart
Voltage Drop per 100ft / 30.5m of Wire (for copper at 68 F / 20 C)