DNP V3.00
28
7.4.4 Analog Output Status Points
Analog Output Status Points
Object Number:
40
Request Function Codes supported:
1 (read)
Default Variation reported
when variation 0 requested:
2 (16-Bit Analog Output Status)
Analog Output Blocks
Object Number:
41
Request Function Codes supported:
3 (select), 4 (operate),
5 (direct operate), 6 (direct operate, noack)
Point
Index
Name/Description
Scaling and Units
(representation of 32767)
Valid Range
0
Float Voltage Setpoint
3276.7 Volts
See Range Section
1
Equalize Voltage Setpoint
3276.7 Volts
See Range Section
2
Equalize Time
32767 Hrs
See Range Section
3
Current Limit
3276.7 Amperes
See Range Section
4
HVDC Setpoint
3276.7 Volts
See Range Section
5
LVDC Setpoint
3276.7 Volts
See Range Section