Chapter IV Function Parameter Table
97
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
current
FE.14 setting range: 0.0
~
6000.0s
FE.15 setting range: 0.0
~
6000.0s
Every FE.15 seconds, apply DC braking
current FE.13 for FE.14 seconds.
FE.14
Defrost
running
time
0.1s
60.0s
×
FE.15
Deicing
operation
interval
0.1s
300.0s
○
FE.16
Signal
source of
water
shortage
Setting range: 0
~
3
0: Use F8.32 function code.
1: Use terminal input
When the multi-function DI terminal is
set to 35, then this terminalis used to
detect water shortage signal.
2: AI1 (0.00
~
10.00V)
3: AI2 (0.00
~
10.00V)
0
0
○
FE.17
Water tank
shortage
threshold
Setting range: 0.0
~
100.0% (100% means
10V)
If FE.16 is set to Ai1 or AI2, it detects the
lack of water in the water tank by using
this threshold. If the feedback is less than
the threshold, the drive will protect and
stop and display E023. Further, all
industrial frequency pumps (auxiliary
pumps) will stop working.
0.1%
10.0%
○
FE.18
Water pipe
leakage
threshold
FE.18 setting range: 0.0
~
30.0% set
pressure value.
FE.19 setting range: 0.0
~
6000.0s
When FE.19 is 0, water pipe leakage
detection is disabled.
When the pressure feedback value is less
than the water pipe leakage threshold
(FE.18), and the operating frequency is
greater than or equal to the upper limit
frequency, a fault will be reported after
the detection time (FE.19), "E034" will be
displayed and the machine will stop
freely.
0.1%
10.0%
○
FE.19
Water pipe
leakage
detection
time
0.1s
0.0s
○
FF group: Water pump protection function 2
FF.00
Flow rate
Setting range: 0.0~5000.0
The flow rate Qn of the pump at rated
frequency and rated head.
Unit: cubic meter/hour
0.1
10.0
×
4.2 Monitoring parameter group U0
Parameter
Code
Parameter
name
Parameter detailed description