HIMA X-AI 32 01 Скачать руководство пользователя страница 1

 

 

X-AI 32 01 

HIMax

®

 

Analog Input Module 

Manual  

 

Содержание X-AI 32 01

Страница 1: ...X AI 32 01 HIMax Analog Input Module Manual...

Страница 2: ...MA directly HIMA appreciates any suggestion on which information should be included in the manual Equipment subject to change without notice HIMA also reserves the right to modify the written material...

Страница 3: ...re 11 3 4 1 Block Diagram 12 3 4 2 Indicators 13 3 4 3 Module Status Indicators 14 3 4 4 System Bus Indicators 15 3 4 5 I O Indicators 15 3 5 Product Data 16 3 6 Connector Boards 18 3 6 1 Mechanical C...

Страница 4: ...ORD 39 4 3 5 Diagnostic Status DWORD 40 4 4 Connection Variants 41 4 4 1 Input Wiring 41 4 4 2 Wiring Transmitters via Field Termination Assembly 44 4 4 3 Redundant Connection via Two Base Plates 45 4...

Страница 5: ...o HIMax System manual Hardware description of the HIMax system HI 801 001 E HIMax Safety manual Safety functions of the HIMax system HI 801 003 E HIMax Communication manual Description of communicatio...

Страница 6: ...d 1 3 1 Safety Notes The safety notes are represented as described below These notes must absolutely be observed to reduce the risk to a minimum The content is structured as follows Signal word danger...

Страница 7: ...e 7 of 58 1 3 2 Operating Tips Additional information is structured as presented in the following example i The text corresponding to the additional information is located here Useful tips and tricks...

Страница 8: ...nt type Range of values Protection class Protection class III in accordance with IEC EN 61131 2 Ambient temperature 0 60 C Storage temperature 40 85 C Pollution Pollution degree II in accordance with...

Страница 9: ...e user program Faults in the wiring 2 3 Safety Precautions Observe all local safety requirements and use the protective equipment required on site 2 4 Emergency Information A HIMax controller is a par...

Страница 10: ...ansmitter supply with a guaranteed minimum voltage The safety function is performed in accordance with SIL 3 3 1 1 Reaction in the Event of a Fault If a fault occurs the module adopts the safe state a...

Страница 11: ...e 32 analog inputs can be used to evaluate the values measured for the transmitters safety transmitters or wired contacts Two wire or three wire transmitters with a maximum supply current of 30 mA can...

Страница 12: ...021 E Rev 4 00 3 4 1 Block Diagram The following block diagram illustrates the structure of the module Field Side Transmitter and Wired Contacts External Transmitter Supply Interface Safety Related P...

Страница 13: ...X AI 32 01 3 Product Description HI 801 021 E Rev 4 00 Page 13 of 58 3 4 2 Indicators The following figure shows the LED indicators for the module Figure 3 Indicators...

Страница 14: ...sfer Table 3 Blinking Frequencies of LEDs 3 4 3 Module Status Indicators These LEDs are located on the front plate on the upper part of the module LED Color Status Description On Module in RUN normal...

Страница 15: ...linking1 The physical connection to the system bus module in slot 2 has been established No connection to a redundant processor module running in system operation A B Off Off Neither physical nor logi...

Страница 16: ...lies max 1 5 A in case of short circuit of the transmitter supplies Current input per channel min 0 mA without transmitter supply min 30 mA with transmitter supply Operating temperature 0 60 C Storage...

Страница 17: ...mperature range 10 C 70 C 0 15 of final value Settling time to 99 of the process value when the input signal changes 15 ms 1 For high precision measurements see Table 11 Table 8 Specifications for the...

Страница 18: ...ds must be used Connector board Description X CB 019 01 Connector board with screw terminals X CB 019 02 Redundant connector board with screw terminals X CB 019 03 Connector board with cable plug X CB...

Страница 19: ...Recess Coding Wedge Guideway for Coding Wedge Figure 5 Coding Example Coded I O modules can be plugged in to uncoded connector boards Uncoded I O modules cannot be plugged in to coded connector board...

Страница 20: ...4a 04b 04c 06a 06b 06c 08a 08b 08c 09a 09b 09c 11a 11b 11c 13a 13b 13c 15a 15b 15c 10a 10b 10c 12a 12b 12c 14a 14b 14c 16a 16b 16c 17a 17b 17c 19a 19b 19c 21a 21b 21c 23a 23b 18a 18b 18c 20a 20b 20c 2...

Страница 21: ...Pin no Designation Signal Pin no Designation Signal 1 09a S9 1 10a S10 2 09b AI9 2 10b AI10 3 09c AI9 3 10c AI15 4 11a S11 4 12a S12 5 11b AI11 5 12b AI12 6 11c AI11 6 12c AI12 7 13a S13 7 14a S14 8...

Страница 22: ...AI31 11 32b AI32 12 31c AI31 12 32c AI32 Table 13 Terminal Assignment for Connector Boards with Screw Terminals Cable plugs attached to the connector board pin headers are used to connect to the fiel...

Страница 23: ...or Boards with Cable Plug Mono Redundant Three fold redundant X CB 008 03 X CB 008 04 X CB 008 07 X CB 019 03 X CB 019 04 I O Module Plug Connection to the Field Zone Cable Plug in Row 1 Connection to...

Страница 24: ...26 BU 1 Not used 8 S25 PK 1 AI25 GY 1 Not used 9 S24 YE 1 AI24 GN 1 Not used 10 S23 BN 1 AI23 WH 1 Not used 11 S22 RD BK AI22 BU BK Not used 12 S21 PK BK AI21 GY BK Not used 13 S20 PK RD AI20 GY RD No...

Страница 25: ...58 3 6 7 Connector Board Redundancy using Two System Base Plates I O Module Plug Connection to the Field Zone Cable Plug in Row 1 Connection to the Field Zone Cable Plug in Row 32 Coding for Cable Pl...

Страница 26: ..._R20 PK RD AI20 GY RD Not used 14 S19 GY RD 1 AI_R19 PK BU AI19 GY BU Not used 15 S18 PK BU 1 AI_R18 YE BK AI18 GN BK Not used 16 S17 GY BU 1 AI_R17 YE RD AI17 GN RD Not used 17 S16 YE BK 1 AI_R16 YE...

Страница 27: ...1 System Cable X CA 005 The X CA 005 system cable is used to connect the X CB 008 03 04 07 and X CB 019 03 04 connector boards to the field zone via field termination assemblies or inline terminals G...

Страница 28: ...anded Average outer diameter d approx 18 3 mm Minimum bending radius Fixed laying Flexible application 5 x d 10 x d Combustion behavior Flame resistant and self extinguishing in accordance with IEC 60...

Страница 29: ...e the appropriate earthing measures when connecting the plugs and terminals to the field zone Use shielded cables with twisted pairs Connect one twisted pair of the shielded cable to each of the analo...

Страница 30: ...lities Screwdriver slotted 0 8 x 4 0 mm Matching connector board To install the connector board 1 Insert the connector board into the guiding rail with the groove facing upwards see following figure F...

Страница 31: ...X AI 32 01 4 Start up HI 801 021 E Rev 4 00 Page 31 of 58 Figure 11 Securing the Connector Board with Captive Screws...

Страница 32: ...ack Move the locks to the open position Lift the cover plate and insert into the fan rack 2 Insert the top of the module into the hook in rail see 3 Swivel the lower edge of the module towards the bas...

Страница 33: ...Removing a Module Swiveling a Module in and out Securing and Releasing a Module Figure 12 Mounting and Removing a Module i If the HIMax system is operating do not open the cover plate of the fan rack...

Страница 34: ...ransmitter supply of the module is used i e Supply ON parameter the Sup used parameter must also be activated for the corresponding channel To diagnose the transmitter supply in use the status Supply...

Страница 35: ...ters can be assigned global variables and used in the user program Module OK BOOL R TRUE Mono operation No module faults Redundant operation At least one of the redundant modules is faultless OR logic...

Страница 36: ...ng the parameter Diagnostic Request see Chapter 4 3 5 for coding details Diagnostic Response DINT R As soon as Diagnostic Response returns the ID of Diagnostic Request see 4 3 5 for coding details Dia...

Страница 37: ...ess value is valid FALSE Faulty channel The process value is set to 0 Sup used BOOL W Activated If a fault occurs in the transmitter supply the module reports a channel fault and sets the input value...

Страница 38: ...ended by the delay time since a signal change is not detected until the delay time has expired Range of values 0 232 1 Default setting 0 State LL BOOL R TRUE Value associated with the LL event state F...

Страница 39: ...A bus 0x00000004 Faults detected while configuring the hardware 0x00000008 Fault detected while verifying the coefficients 0x00000080 Reset of the chip select monitoring 0x10000000 Fault during AD con...

Страница 40: ...032 Status of the channels 1 32 Coding Description 0x0001 Hardware unit fault submodule occurred 0x0002 Reset of an E A bus 0x0400 SC OC limits exceeded or channel module fault 0x0800 Measured values...

Страница 41: ...he transmitter supplies of two modules can supply one transmitter if the modules are redundant to one another Connector boards X CB 008 01 and X CB 019 01 with screw terminals or X CB 008 03 and X CB...

Страница 42: ...e plate next to each other and on a common connector board Connector boards X CB 008 02 and X CB 019 02 with screw terminals or X CB 008 04 and X CB 019 04 with cable plug can be used X AI 32 01 Conne...

Страница 43: ...21 E Rev 4 00 Page 43 of 58 X AI 32 01 Connector Board AI S S AI AI_R X AI 32 01 AI S S AI AI_R 1 2 3 2 3 External Transmitter Supply Transmitter Supply Analog Input Figure 16 Redundant Connection of...

Страница 44: ...For further information refer to the X FTA 002 01 Manual HI 801 117 E AI S Connector Board S1 AI1 AI1_R X AI 32 01 Field Termination Assembly X FTA 002 01 A1 B1 AI S S32 AI 32 AI 32_R X AI 32 01 B32 C...

Страница 45: ...s the connection of one transmitter if the redundant modules inserted in different base plates or are not located in the base plate adjacently The instrument shunts are placed on the field termination...

Страница 46: ...Analog Input Figure 19 Single Channel Transmitter Connection with Barrier 4 4 5 EX Protection with Repeater Power Supply Analog power supply isolators such as the H 6200A from HIMA can be implemented...

Страница 47: ...fluctuation caused by the HART communications is removed using filters on the analog input so that the residual error of the analog measurement is 1 i Higher residual error with HART communication Re...

Страница 48: ...the SILworX documentation 5 2 Diagnosis LEDs on the front side of the module indicate the module state see Chapter 3 4 2 The diagnostic history of the module can also be read using SILworX Chapter 4 3...

Страница 49: ...usly improving the operating system of the module HIMA recommends to use system downtimes to load the current version of the operating system into the module For detailed instructions on how to load t...

Страница 50: ...7 Decommissioning X AI 32 01 Page 50 of 58 HI 801 021 E Rev 4 00 7 Decommissioning To decommission the module remove it from the base plate For more information see Mounting and Removing the Module...

Страница 51: ...id mechanical damage HIMax components must be transported in packaging Always store HIMax components in their original product packaging This packaging also provides protection against electrostatic d...

Страница 52: ...21 E Rev 4 00 9 Disposal Industrial customers are responsible for correctly disposing of decommissioned HIMax hardware Upon request a disposal agreement can be arranged with HIMA All materials must be...

Страница 53: ...ra Low Voltage PES Programmable Electronic System PFD Probability of Failure on Demand probability of failure on demand of a safety function PFH Probability of Failure per Hour probability of a danger...

Страница 54: ...th Captive Screws 31 Figure 12 Mounting and Removing a Module 33 Figure 13 Single Channel Connection of a Passive Two Wire Transmitter 41 Figure 14 Single Channel Connection of an Active Two Wire Tran...

Страница 55: ...cision Measurements 18 Table 12 Position of Coding Wedges 19 Table 13 Terminal Assignment for Connector Boards with Screw Terminals 22 Table 14 Cable Plug Properties 22 Table 15 Pin Assignment for the...

Страница 56: ...block diagram 12 connector board 18 with cable plug 23 with screw terminals 20 diagnosis 48 I O indicators 15 system bus indicators 15 HART communication 47 module status indicators 14 safety functio...

Страница 57: ......

Страница 58: ...aul Hildebrandt GmbH Co KG HIMax and SILworX are registered trademark of HIMA Paul Hildebrandt GmbH Co KG Albert Bassermann Str 28 68782 Br hl Germany Phone 49 6202 709 0 Fax 49 6202 709 107 HIMax inf...