4 Start-up 

X-SB 01 

Page 24 of 38 

HI 801 007 E Rev. 4.00 

4.3 

Configuring the Module in SILworX 

The module is configured in the Hardware Editor of the SILworX programming tool. 

The following tables present the statuses and parameters for the module in the same order 
given in the SILworX Hardware Editor. 

4.3.1 Tab: 

Module 

The 

Module

 tab contains the statuses and parameters for the module. 

System parameter 

Description 

Name Module 

name 

IP Address 

IP address of the Ethernet interface. 

Subnet Mask 

Subnet mask of the Ethernet interface 

Speed Mode 

Transfer rate: 

ƒ

 10 

Mbit/s 

ƒ

 100 

Mbit/s 

ƒ

 Autoneg 

HIMA recommends to maintain the 

Autoneg 

default setting. 

Flow Control Mode 

Operational mode of the flow control: 

ƒ

 Half 

Duplex 

ƒ

 Full 

Duplex 

ƒ

 Autoneg 

 

HIMA recommends to maintain the 

Autoneg 

default setting. 

Standard Interface 

Activated: the interface is used as standard interface for the system 
login. 
Deactivated: the interface is not used as standard interface for the 
system login. 
Default setting: Deactivated  

Default Gateway 

IP address of the default gateway. 

ARP Aging Time [s] 

A system bus module stores the MAC addresses of the 
communication partners in a MAC/IP address assignment table 
(ARP cache). 
If in a period of 1x....2x 

ARP Aging Time

 ... 

ƒ

  ... messages of the communication are received, the MAC 

address remains stored in the ARP cache. 

ƒ

  ... no messages of the communication partner are received, the 

MAC address is erased from the ARP cache. 

 
The typical value for the 

ARP Aging Time

 in a local network ranges 

from 5...300 s. 
The user cannot read the contents of the ARP cache. 
 
Range of values: 1...3600 s 
Default value: 60 s 

 
Note:

 

If routers or gateways are used, the user must adjust (increase) the 

ARP Aging Time

 due to the additional time required for two-way 

transmission. 
If the 

ARP Aging Time 

is too low, the MAC address of the 

communication partner is erased from the ARP cache, the 
communication is delayed or interrupted

.

 For an efficient 

performance, the ARP aging time value must be less than the 
receive timeout set for the protocols in use. 

 

Содержание HIMax X-SB 01

Страница 1: ...X SB 01 HIMax System Bus Module Manual...

Страница 2: ...t HIMA directly HIMA appreciates any suggestion on which information should be included in the manual Equipment subject to change without notice HIMA also reserves the right to modify the written mate...

Страница 3: ...the Event of a Fault 10 3 2 Scope of Delivery 10 3 3 Type Label 11 3 4 Structure 12 3 4 1 Block Diagram 12 3 4 2 Safety Related Processor System 12 3 4 3 Interfaces 13 3 4 4 Indicators 14 3 4 5 Module...

Страница 4: ...ation 27 5 1 Handling 27 5 2 Diagnosis 27 6 Maintenance 28 6 1 Maintenance Measures 28 6 1 1 Loading the Operating System 28 6 1 2 Proof Test 28 7 Decommissioning 29 8 Transport 30 9 Disposal 31 Appen...

Страница 5: ...HIMax System manual Hardware description of the HIMax system HI 801 001 E HIMax Safety manual Safety functions of the HIMax system HI 801 003 E HIMax Communication manual Description of communication...

Страница 6: ...1 3 1 Safety Notes The safety notes are represented as described below These notes must absolutely be observed to reduce the risk to a minimum The content is structured as follows Signal word danger...

Страница 7: ...7 of 38 1 3 2 Operating Tips Additional information is structured as presented in the following example i The text corresponding to the additional information is located here Useful tips and tricks a...

Страница 8: ...type Range of values Protection class Protection class III in accordance with IEC EN 61131 2 Ambient temperature 0 60 C Storage temperature 40 85 C Pollution Pollution degree II in accordance with IE...

Страница 9: ...user program Faults in the wiring 2 3 Safety Precautions Observe all local safety requirements and use the protective equipment required on site 2 4 Emergency Information A HIMax controller is a part...

Страница 10: ...of the modules Further the module provides an interface to the programming and debugging tool PADT The module has been certified by the T V for safety related applications up to SIL 3 IEC 61508 IEC 6...

Страница 11: ...bel specifies the following important details Product name Mark of conformity Bar code 2D or 1D code Part number Part No Hardware revision index HW Rev Software revision index SW Rev Operating voltage...

Страница 12: ...re of the module Safety Related Processor System System Bus Controller System Bus A or System Bus B Figure 2 Block Diagram 3 4 2 Safety Related Processor System The safety related 1oo2 processor syste...

Страница 13: ...lex Auto Negotiation Yes Auto Crossover No Connection socket RJ 45 IP Address Freely configurable Subnet Mask Freely configurable Table 3 Specifications for the Service Interface i The service interfa...

Страница 14: ...3 Product Description X SB 01 Page 14 of 38 HI 801 007 E Rev 4 00 3 4 4 Indicators The following figure shows the LED indicators for the module Figure 3 Indicators...

Страница 15: ...communication Flashing in sync with data transfer Table 5 Blinking Frequencies of LEDs 3 4 5 Module Status Indicators These LEDs are located on the front plate on the upper part of the module LED Col...

Страница 16: ...lly allocates identical system rack IDs the adjustment of the system rack IDs was successful Blinking1 Redundancy setting Red Yellow Off No redundant operation Table 7 Redundancy Indicators 3 4 7 Rack...

Страница 17: ...ddress conflict detected LEDs adjacent to one another PADT and H F Col blinking PADT Green Off PADT not connected On Speed 100 Mbit s Blinking x not defined Blinking1 IP address conflict detected LEDs...

Страница 18: ...ply voltage 24 VDC 15 20 rP 5 SELV PELV Current input max 0 65 A Operating temperature 0 60 C Storage temperature 40 85 C Humidity max 95 relative humidity non condensing Type of protection IP20 Dimen...

Страница 19: ...te one left connector board L for slot 1 and one right connector board R for slot 2 The connector boards contain information on the number of modules 10 15 or 18 that can be inserted into the base pla...

Страница 20: ...nterface PADT X1 Connection for the PADT External system bus interfaces UP X2 Connection for additional HIMax base plates DOWN X3 Connection for additional HIMax base plates External diagnostic interf...

Страница 21: ...Observe the following points when mounting the module Only operate the module with the appropriate fan components For more information see the System Manual HI 801 001 E Operation is only allowed wit...

Страница 22: ...the module in the base plate Tools and utilities Screwdriver slotted 0 8 x 4 0 mm Screwdriver slotted 1 2 x 8 0 mm Installation 1 Open the cover plate on the fan rack Move the locks to the open posit...

Страница 23: ...emoving a Module Swiveling a Module in and out Securing and Releasing a Module Figure 6 Mounting and Removing a Module i If the HIMax system is operating do not open the cover plate of the fan rack fo...

Страница 24: ...ce is not used as standard interface for the system login Default setting Deactivated Default Gateway IP address of the default gateway ARP Aging Time s A system bus module stores the MAC addresses of...

Страница 25: ...e important than the authorized access to the controller Default setting Conservative IP Forwarding Allow a system bus module to operate as router and to forward data packets to other network nodes De...

Страница 26: ...dress with subnet routing Range of values 0 0 0 0 255 255 255 255 Default value 0 0 0 0 Subnet Mask Define the target address range for a routing entry 255 255 255 255 with direct host routing or subn...

Страница 27: ...more details refer to the SILworX documentation 5 2 Diagnosis LEDs on the front side of the module indicate the module state see Chapter 3 4 4 The diagnostic history of the module can also be read usi...

Страница 28: ...ly improving the operating system of the module HIMA recommends to use system downtimes to load the current version of the operating system into the module For detailed instructions on how to load the...

Страница 29: ...X SB 01 7 Decommissioning HI 801 007 E Rev 4 00 Page 29 of 38 7 Decommissioning To decommission the module remove it from the base plate For more information see Mounting and Removing the Module...

Страница 30: ...d mechanical damage HIMax components must be transported in packaging Always store HIMax components in their original product packaging This packaging also provides protection against electrostatic di...

Страница 31: ...ge 31 of 38 9 Disposal Industrial customers are responsible for correctly disposing of decommissioned HIMax hardware Upon request a disposal agreement can be arranged with HIMA All materials must be d...

Страница 32: ...9 Disposal X SB 01 Page 32 of 38 HI 801 007 E Rev 4 00...

Страница 33: ...a Low Voltage PES Programmable Electronic System PFD Probability of Failure on Demand probability of failure on demand of a safety function PFH Probability of Failure per Hour probability of a dangero...

Страница 34: ...ge 34 of 38 HI 801 007 E Rev 4 00 Index of Figures Figure 1 Sample Type Label 11 Figure 2 Block Diagram 12 Figure 3 Indicators 14 Figure 4 Views 18 Figure 5 Connector Boards 19 Figure 6 Mounting and R...

Страница 35: ...he System Bus Interface 13 Table 5 Blinking Frequencies of LEDs 15 Table 6 Module Status Indicators 15 Table 7 Redundancy Indicators 16 Table 8 Rack Connection Indicators 16 Table 9 Slot Indicators 17...

Страница 36: ...01 007 E Rev 4 00 Index connector boards 19 diagnosis 27 rack connection indicators 16 slot indicators 17 interfaces 13 module status indicators 15 Processor System 12 specifications 18 service interf...

Страница 37: ......

Страница 38: ...aul Hildebrandt GmbH Co KG HIMax and SILworX are registered trademark of HIMA Paul Hildebrandt GmbH Co KG Albert Bassermann Str 28 68782 Br hl Germany Phone 49 6202 709 0 Fax 49 6202 709 107 HIMax inf...

Отзывы: