4 Start-up
X-MIO 7/6 01
Page 48 of 72
HI 801 305 E Rev. 5.00
Name
Data
type
R/W Description
Timestamp [µs]
DWORD R
Microsecond fraction of the timestamp.
Time point of the sampling performed by the processor system
of the I/O module.
Timestamp [s]
DWORD R
Second fraction of the timestamp.
Time point of the sampling performed by the processor system
of the I/O module.
Trigger Trip
BOOL
W
TRUE: Trigger trip through user program
FALSE: Do not trigger trip through user program
Default setting: FALSE
Trip Existing
BOOL
R
TRUE: Trip function triggered
FALSE: Trip function not triggered
Trip State
DWORD R
Status of the Trip State parameter
Coding
Description
0x00000002 Threshold violated (rotation speed)
0x00000004 Grandient violated (acceleration)
0x00000008 Trip triggered through digital input
0x00000010 Trip triggered through user program
0x00000020 One or no channel is available for
gradient monitoring.
Warning Existing
BOOL
R
TRUE: Warning existing, relay DO 06 de-energized
FALSE: No warning, relay DO 06 energized
Table 27: Module Tab in the Hardware Editor