3 Product Description
X-DO 24 01
Page 18 of 52
HI 801 019 E Rev. 4.00
Digital Outputs
Number of outputs (number of channels)
24, non-electrically isolated
Output voltage
≥
L+ minus internal voltage drop
Voltage drop (with high level)
0.8 V at 0.75 A output current
Nominal rated current (with high level)
0.5 A, range 0.01...0.6 A
Total current permitted for the module
12 A
Leakage current (with low level)
max. 500 µA
Current limiting in the event of short-circuit approx. 2 A, each channel
Overcurrent interruption
I > 0.75 A for t > 50 ms
Ohmic load
To nom. rated current 0.5 A
Inductive load
max. 50 H
Lamp load (24 V lamps)
max. 4 W
Capacitive load
max. 100 µF
Line monitoring
OC Limit
≤
4 mA
SC Limit
> 0.75 A (range 0.75...0.8 A)
Overload protection of the outputs,
transient
33 V (max. 43 V)
Switching time of the channels (with ohmic
load)
100 µs
Test impulse (with ohmic load)
typ. 200 µs
Behavior upon overload
The affected output is switched off and re-
started cyclically.
Table 8:
Specifications for the Digital Outputs