X-CPU 01
4 Start-up
HI 801 009 E Rev. 4.00
Page 37 of 52
Mirroring
Mirroring is used to configure whether the module should duplicate Ethernet packets on a
given port such that they can be read from a device connected to that port, e.g., for test
purposes.
The following parameters define how a given port should work:
Off
This port does not participate to the mirroring process.
Egress:
Outgoing data of this port are duplicated.
Ingress:
Incoming data of this port are duplicated.
Ingress/Egress: Incoming and outgoing data of this port are duplicated.
Dest Port:
This port is used to send duplicated data.
Default setting: OFF
4.1.5
Configuring Events in SILworX
Event Definition
1. Define a global variable for each event. Generally use global variables that have already
been defined for the program.
2. Below the resource, create a new
Alarm & Events
branch, if not existing.
3. Define events in the Alarm & Event Editor.
-
Drag global variables into the event window for Boolean or scalar events.
-
Define the details of the events, see Table 22 and Table 23.
The events are defines.
For further information, refer to the SILworX online help.
The parameters of the Boolean events must be entered in a table with the following
columns: