3 Product Description
X-COM 01
Page 16 of 42
HI 801 011 E Rev. 5.00
The LEDs on the module are divided into three groups:
Module status indicators (Run, Error, Stop, Init)
System bus indicators (A, B)
Fieldbus indicators (1, 2, Fault)
Communication indicators (Ethernet)
When the supply voltage is switched on, a LED test is performed and all LEDs are briefly lit.
Definition of blinking frequencies
The following table defines the blinking frequencies of the LEDs:
Name
Blinking frequencies
Blinking1
Long (approx. 600 ms) on, long (approx. 600 ms) off
Blinking2
Short (approx. 200 ms) on, short (approx. 200 ms) off, short (approx. 200 ms)
on, long (approx. 600 ms) off
Blinking-x
Ethernet communication: Blinking synchronously with data transfer
Table 8:
Blinking Frequencies of LEDs
3.4.4
Module Status Indicators
These LEDs are located on the front plate, on the upper part of the module.
LED
Color
Status
Description
Run
Green
On
Module in RUN, normal operation
Blinking1
Module state:
STOP/OS_DOWNLOAD or
OPERATE (only with processor modules)
Off
Module not in RUN,
observe the other status LEDs
Error
Red
On/Blinking1
Internal module faults detected by self-tests, e.g.,
hardware or voltage supply.
Fault while loading the operating system
Off
Normal operation
Stop
Yellow
On
Module state:
STOP / VALID CONFIGURATION
Blinking1
Module state:
STOP / INVALID CONFIGURATION or
STOP / OS_DOWNLOAD
Off
Module not in STOP, observe the other status LEDs
Init
Yellow
On
Module state: INIT
Blinking1
Module state:
LOCKED or
STOP / LOADING OS
Off
Module state: neither INIT nor LOCKED, observe the
other status LEDs
Table 9:
Module Status Indicators