System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 51 of 114
7.2.3
Mounting on a Flat Base
The F60 subrack is equipped with two perpendicular joint bars each of which has two oblong
holes for fastening. These joint bars must be secured on a flat base.
The mounting bolts must not exceed 6 mm in diameter and 13 mm head diameter. The screws
and the selected base must be suitable to hold the weight of the controller.
Figure 9: Securing the F60 Subrack
7.2.4
Mounting and Removing the Modules
To mount and remove the modules, the connection cable clamp terminals must be unplugged.
Mounting the Modules
To mount a module into the subrack
1. Insert the module as far as it can go
– without jamming it – into the two guiding rails which
are located on the housing's upper and lower part.
2. Apply pressure to the upper and lower extremity of the front plate until the module plugs
snap into the backplane socket.
3. Secure the module with the screws located on upper and lower extremity of the front plate.
The module is mounted.
Removing the Modules
To remove a module from the subrack
1. Remove the plugs from the module front plate.
2. Release the locking screws located on the upper and lower extremity of the front plate.
3. Loosen the module using the handle located on the lower part of the front plate and remove
it from the guiding rails.
The module is removed.
7.2.5
Connecting the Input and Output Circuits
To attach the cables and connected the shielding
1. Led the cables vertically downwards and secure them with 2 cable straps to the earth grid
guide.