4 Start-up
F3 DIO 8/8 01
Page 36 of 52
HI 800 179 E Rev. 2.00
4.3.4.2
Tab
DO 2 01: DO1 Channels
The
DO 2 01: DO1 Channels
tab contains the following system parameters:
System parameter
Data type R/W
Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital output channels
Coding
Description
0x01
Fault in the digital output module
0x02
Channel shutdown due to overload
0x04
Error while reading back the digital outputs
0x08
Error while reading back the status of the
digital outputs
0x40
External short-circuit or short-circuit of the
EMC protection returns an error
0x80
Channel is switched off due to fault on the
corresponding channel
Value [BOOL] ->
BOOL
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Table 28: SILworX - System Parameters for Digital Outputs,
DO 2 01: DO1 Channels
Tab
Содержание HIMatrix F3 DIO 8/8 01
Страница 46: ...9 Disposal F3 DIO 8 8 01 Page 46 of 52 HI 800 179 E Rev 2 00...