F3 AIO 8/4 01
4 Start-up
HI 800 161 E Rev. 2.00
Page 39 of 56
System signal
R/W
Description
Transmitter
Voltage[01] [USINT]
W
Switching of the transmitter supply for each group:
1 = 8.2 V
2 = 26.0 V
Transmitter.
Error Code [WORD]
R
Error codes for the transmitter unit
Coding
Description
0x0001
Fault in the transmitter supply
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
Transmitter[01].
Error Code [BYTE]
R
Error codes for each transmitter group
Coding
Description
0x01
Module fault of transmitter supply
0x02
Overcurrent of transmitter supply
0x04
Undervoltage of transmitter supply.
0x08
Overvoltage of transmitter supply.
AI[xx].Underflow
[BOOL]
R
Underflow
AI[INT].Value
in accordance with
AI[xx].Limit Value LOW
The validity depends on
AI[xx].Error Code
AI[xx].Overflow
[BOOL]
R
Overflow
AI[INT].Value
in accordance with
AI[xx].Limit Value HIGH
The validity depends on
AI[xx].Error Code
AI[xx].Threshold
LOW
[INT]
W
Voltage range upper limit for low level
AI[xx].Underflow
AI[xx].Limit Value
HIGH
[INT]
W
Voltage range low limit for high level
AI[xx].Overflow
Table 33: ELOP II Factory - System Signals for the Analog Inputs