4 Start-up
F3 DIO 16/8 01
Page 46 of 60
HI 800 177 E Rev. 2.00
4.5
Configuration of Line Diagnosis
4.5.1
Line Diagnosis for Lamp Loads and Inductive Loads
To detect short-circuits, a 24 V pulse (normal voltage level) is sent to the output circuit for the
duration of 500 µs. After this time, a 10 V pulse is sent to detect open-circuits for the duration of
the monitoring time.
To configure the line diagnosis, the following parameters must be set in SILworX and the
following signals must be set in ELOP II Factory Hardware Management.
SILworX
ELOP II Factory
Value
DO.LM period
DO.LSLB Interval
Freely configurable
1…100 s
DO.Line Monitoring Time
DO.LSLB Monitoring Time
Freely configurable
0…50 ms
Default: 0 ms
2-pole [BOOL] ->
DO[xx].2-Pole
TRUE
Line Monitoring [BOOL] ->
DO[xx].LSLB Monitoring
TRUE
DO[xx].SC Monitoring with
Reduced Voltage
DO[xx].SC Monitoring with
Reduced Voltage
FALSE
Table 33: Configuration of Line Diagnosis for Lamp Loads and Inductive Loads
4.5.2
Line Diagnosis for Ohmic, Capacitive Loads
To diagnose the line for ohmic capacitive loads, the remote I/O sends a 10 V test pulse
(reduced voltage level) to the output circuit for the duration of the monitoring time. This type of
line diagnosis is particularly recommended for ohmic and ohmic capacitive loads. With inductive
loads or lamp loads, error messages related to the short-circuit may be generated.
To configure the line diagnosis, the following parameters must be set in SILworX and the
following signals must be set in ELOP II Factory Hardware Management.
SILworX
ELOP II Factory
Value
DO.LM period
DO.LSLB Interval
Freely configurable
1…100 s
DO.Line Monitoring Time
DO.LSLB Monitoring Time
Freely configurable
0…50 ms
Default: 0 ms
2-pole [BOOL] ->
DO[xx].2-Pole
TRUE
Line Monitoring [BOOL] ->
DO[xx].LSLB Monitoring
TRUE
DO[xx].SC Monitoring with
Reduced Voltage
DO[xx].SC Monitoring with
Reduced Voltage
TRUE
Table 34: Configuration of Line Diagnosis with Reduced Voltage with Ohmic, Capacitive Loads