CPU 01
3 Product Description
HI 800 189 E Rev. 1.01
Page 11 of 40
3 Product
Description
The CPU 01 module is the central component of the HIMatrix F60 controller.
The module can only be inserted in the slot located on the right, next to the power supply
module of the HIMatrix F60 subrack. It is used to store the operating system and the user
program, and executes all central functions, including communication with the PADT and
other systems. It monitors the operating voltage and operating temperature.
The module has been certified by the TÜV for safety-related applications up to SIL 3 (IEC
61508, IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further
safety standards, application standards and test standards are specified in the certificate
available on the HIMA website.
Module's faults are signaled by the
ERR
LED located on the front plate, see Chapter 3.4.3.
3.1 Safety
Function
The CPU monitors the sequence and the proper, logical execution of the operating system
and user program. The following functions are time monitored:
CPU hardware and software self-tests
CPU RUN cycle (including the user program)
I/O tests and processing of I/O signals
For further information on the fault reaction of the processor module, refer to Chapter 6.1.
3.2
Equipment, Scope of Delivery
The following list specifies the available components and the corresponding part numbers:
Designation
Description
Part no.
CPU 01
Central module, for ELOP II Factory programming tool 98 2200126
CPU 01 SILworX
Central module, for SILworX programming tool
98 2200137
Table 4:
Part Numbers
3.2.1
IP Address and System ID (SRS)
A transparent label is delivered with the device to allow one to note the IP address and the
system ID (SRS for system rack slot) after a change.
IP___.___.___.___SRS____.__.__
Default value for IP address:
192.168.0.99
Default value for SRS:
60000.200.0 (SILworX)
60000.0.0
(ELOP
II
Factory)
The label must be affixed such that the ventilation slots in the housing are not obstructed.
Refer to the First Steps manual of the programming tool for more information on how to
modify the IP address and the system ID.