Technical Data
60/86
netTAP NT 50 | Gateway Devices
DOC091202UM09EN | Revision 9 | English | 2013-02 | Released | Public
© Hilscher, 2010-2013
9.3.2 CANopen
Slave
Parameter
Description
Maximum number of cyclic input data
512 bytes
Objects 2200, 2201, 2202, 2203 each with up to 128 bytes
Maximum number of cyclic output data
512 bytes
Objects 2000, 2001, 2002, 2003 each with up to 128 bytes
Maximum number of receive PDOs
64
Maximum number of transmit PDOs
64
Exchange of process data
Via PDO transfer
- synchronized,
- remotely requested and
- event driven (change of date, event timer)
Functions
Node guarding / life guarding, heartbeat
PDO mapping
NMT Slave
SYNC protocol (consumer)
SDO upload/download (server, for configuration)
Emergency message (producer)
Baud rates
10 kBits/s,
20 kBits/s,
50 kBits/s,
100 kBits/s,
125 kBits/s,
250 kBits/s,
500 kBits/s,
800 kBits/s,
1 MBits/s
Auto baudrate detection is supported
Data transport layer
CAN Frames
CAN Frame type for CANopen
11 Bit
Limitations
Timestamp (producer/consumer) not supported on application
level.
Reference to stack version
V3.0.x.x
Table 58: Technical Data CANopen Slave Protocol
Configuration of the node address
The CANopen node address can be configured by SYCON.net or by ad-
dress switches. The address switches can be activated with SYCON.net
version 1.351 (or higher) and can be used with firmware version 1.1 (or
higher).