Mounting and dismounting of netHOST device
40/75
6.2
Mounting netHOST device onto Top Hat Rail
Ø
The netHOST device is to be mounted onto a horizontally attached top
hat rail according to DIN EN 60715.
Ø
The rail has to be connected with the potential equalization conductor
(PE).
Ø
The devices can be mounted onto the top hat rail side-by-side without
any gap.
(1)
(2)
Ø
Push the device onto the top hat rail from above.
Ø
Then press the device against the mounting surface.
Table 31: Mounting the netHOST device onto Top Hat Rail
Ø
After mounting, connect the 24 V supply voltage to the device.
Device Destruction by Exceeding the Allowed Supply Voltage!
The supply voltage must not exceed 30 V, otherwise the netHOST device
will be damaged.
Note:
Grounding is done via a grounding contact located at the backside
of the device, connecting it electrically to the DIN top hat rail.
netHOST NHST-T100 | LAN controlled master devices
DOC130401UM05EN | Revision 5 | English | 2018-05 | Released | Public