Configuration
65/146
8.3.8.3
Port settings
Use the Settings tab to view and change the port settings individually.
Ø
Select the desired wireless port (WP01, WP02, WP03, ...) in the left
column of the netFIELD Wireless Web Server.
Ø
Open the
Settings
tab with its sub tabs.
Ê
The Port cycle sub tab appears by default.
Settings > Port cycle
Figure 26: Settings tab, Port cycle sub tab (example)
Parameter
Description
Value / Value range
Port mode
Operating mode of IO-Link port
·
Deactivated: The port is inactive, Input and Output Process Data
is 0.
·
Cyclic
·
Roaming
Deactivated, Cyclic, Roaming,
Default: Deactivated
Port cycle time
Port cycle time expected by the
The expected cycle time of the port is set depending on the
selected operating parameters.
cycle time of the IO-Link
Wireless Master
Time base: Used time base for the calculation of the port cycle
time.
Free running, 5 ms
Time multiplier: Used factor for the calculation of the port cycle
time.
0 … 63
Table 37: Settings in port configuration for IO-Link Device, Port cycle sub tab
* Values are in hexadecimal
Ø
Configure port operating mode
Port mode
by selecting the
corresponding option.
Ø
Configure the “Port cycle time”.
The parameter “Port cycle time” sets up the cycle time of a W-Port of the
W-Master. The cycle time is encoded using "Time base" (bits 6+7) and
"Multiplier" (bits 0-5) values, as shown in the following table:
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public
© Hilscher 2020 - 2022