5. Grasp the replacement fan tray with the screws on the right side of your palm. Slide the fan
tray into the slot until you feel resistant.
6. Use a cross screwdriver clockwise to tighten two screws on the fan tray.
Notes: To prevent over-heating, you should install the replacement fan tray within
one minute after the existing fan tray is removed. If system detects over-heating, it
will automatically switch off the power supply. You are suggested to buy the backup
fan trays firstly before maintaining the cooling system.
Replacing a Fan Tray of SG-6000-X8180
To replace a fan tray, take the following steps:
1. Wear an electrostatic discharge (ESD) strap around your bare wrist and connect the strap to
an ESD point on the chassis. See
.
2. Use a cross screwdriver to loosen the screws on the fan tray.
3. Hold the handle of the fan tray and pull it out a little to disconnect it to power. Wait till the
fans stop spinning.
4. After the fans have stopped spinning, pull the fan tray out of chassis.
Chapter 5 Hardware Maintenance and
Replacement
146
Содержание SG-6000 X Series
Страница 1: ...Hillstone SG 6000 X Series Hardware Reference Guide TechDocs docs hillstonenet com...
Страница 11: ...Troubleshooting the Configuration System 156 Appendix Supported Versions of Devices 158 TOC 9...
Страница 38: ...SCM 260 SCM D1T 260 SCM D2T 260 is shown as below SCM 100 SCM 20 is shown as below 26 Chapter 1 Product Profile...
Страница 40: ...SSM 100 SSM 80 is shown as below SSM 20 is shown as below 28 Chapter 1 Product Profile...
Страница 45: ...IOM 16SFP 100 is shown as below IOM 4XFP 100 is shown as below Chapter 1 Product Profile 33...
Страница 48: ...SIOM P100 300 is shown as below SIOM P100 260 is shown as below 36 Chapter 1 Product Profile...
Страница 80: ...Chapter 2 Installation Preparations 68...
Страница 83: ...71 Chapter 2 Installation Preparations...
Страница 84: ...Chapter 2 Installation Preparations 72...
Страница 85: ...73 Chapter 2 Installation Preparations...