HF-VS409
Diagram References
E N G L I S H
UD24995B
1. Pull out the green connector inside the Alarm In/Out Interface.
2. Loosen the screws with a mini slotted screwdriver, put in the cable and tighten the screws.
3. Plug the connector into the green base.
Note: The requirement of the mounting location is shown as the figure.
1. Accessories that you need to prepare for installation: Junction box (Optional).
2. If the mounting location (such as the ceiling) is longer than 10 meters, multiple detectors
need to be installed.
3. The installation parameters should be subject to EN14604 Code for Design of Automatic
Fire Alarm System".
4. Avoid installing the detector in the following locations:
-Kitchens, hot water heaters, bathrooms and other high-humidity spaces.
-Air conditioners, fans, heating outlets, and strong convection locations.
-Places that are dusty, dirty, or frequented by insects.
-High temperature and easily polluted places such as stoves.
-Where the object is obscured.
-Places within 1.5 meters of the light.
-The upper part of the spire house, the corner of the room and other closed spaces.
Before you begin:
Pull out the plug
Plastic Expansion Sleeves
Mounting Template
Mounting Base
Screws
Smoke Detector
Plastic Expansion Sleeves
Mounting Template
Junction Box
Screws
Smoke Detector
Mounting Base
Screws
19.69''(500 mm)
Minimum distance
from the side wall
Power Interface
Alarm In/Out Interface
Network
Interface
Alarm Input
Device
Alarm Output
Device
Illustration
Appearance
Wiring Description
Installation
1
2
3
microSD Card Slot
Indicator
TAMPER
RESET Button
TEST/SILENCE Button
Camera
1
5
6
2
3
4
2
3
4
5
6
1
1
3.1
3.2
2
Note: The appearance of the device vary according to different model. Refers to the actual device.
Refers to the figure for the details of the terminal.
Mounting Location
Ceiling Mounting
3.1
3.2
Ceiling Mounting without Junction Box
1.
Drill 4 screw holes on the ceiling according to the mounting template.
2.
Insert the plastic expansion sleeves into the screw holes, and fix the mounting base with screws.
3.
Smooth the cables and turn the smoke detector clockwise until it snaps in place.
Ceiling Mounting with Junction Box
1.
Drill 4 screw holes on the ceiling according to the mounting template.
2.
Insert the plastic expansion sleeves into the screw holes, and fix the junction box with screws.
3. Fix the mounting base to the junction box with screws.
3.
Smooth the cables and turn the smoke detector clockwise until it snaps in place.
Configuration
4
You should activate the device before the first login.
Enter the device IP address in the address bar of the web browser to login.
You can configure and operate the device. Scan the QR code for details.
Activation
Configuration and Operation via Web
Local Settings
Connect your device to Ethernet, and you can configure parameters of the device via browser.
Network Settings
Default IP Address: 192.168.1.64
Activation via SADP tool, the client software and the web browser are supported. Refers to the
User Manual for details.Here takes activation via web browser for example.
1. Connect the device to your computer with network cable. Make sure the device IP address and
the computer's should be in the same IP segment.
2. Power on the device.
3. Enter the device IP address in the address bar of the web browser, and press
Enter
to create
admin account. Click
OK
to activate the device.
Smoke/Temperature Alarm
In standby mode, when smoke particles or the temperature reach the settings, the alarm will be
triggered.
The buzzer will beep and the indicator keeps red.
You can enable the function via web to upload the alarm records, smoke concentration and
pollution data to platforms and FTP. Scan the QR Code to see the User Manual for details.
TEST
Make sure the buzzer and indicator work properly.
In standby mode, press the
TEST/SILENCE
button, and the device will enter test mode. After
testing, the device will exit the test mode automatically.
Test Mode: The buzzer beeps for 10 times, and the indicator keeps red.
Mute
In alarm mode, hold the
TEST/SILENCE
button to mute the alarm (the mute period is 10 minutes).
Mute Mode: The buzzer stops beeping, and the indicator keeps red.
Mute Period: After the alarm is mute, if the smoke concentration or the temperature still reach
the settings, the alarm will be triggered in 10 minutes.
Reset
When the alarm is in mute mode(when the red light keeps red and the buzzer stops beeping),
press the
TEST/SILENCE
button again to reset the device.
In alarm mode, if the smoke dissipates or the temperature declines, the alarm will automatically
resume to standby mode.
Default Setting
Hold the RESET button and power on the alarm. Hold the button for 10 to 15 seconds while the
device is powered on. Release the button and the device will be restored to default settings.
1
2
3
4
Refers to Smoke Detected Camera User
Manual (scan the QR code) for details.
Indicator
Buzzer
Status
Flashing Green every 90 s
Disable
Standby Mode
Bolid Red
Squeal
Smoke/Temperature Alarm
Flashing Red every 40 s
Beeping Once every 40 s
Low Voltage
Quick Flashing Green 3 times
Disable
Tampering Alarm
Flashing Yellow every 40 s
Beeping for every 40 s
Maze Pollution
Flashing Red every 100 s
Disable
Temperature Sensor Fault
Visual
S
moke
Detection
Camera