HighCross Ltd.
OVERVIEW
DEVICE CONTROL COMPONENTS
Number of serial ports
2
Supported interfaces of
serial ports
RS232, RS485, DMX512
Supported signals of
physical interfaces
RS232: GND, TX, RX, RTS, CTS
RS485, DMX512: A(–), B(+)
Isolation of serial ports
Up to 1 kV
Supply voltage range
12–24 VDC via power terminals
48 VDC via PoE port
Consumption current
200 mA @ 12 VDC
Operating temperature
-20° C to 45° C
-5° F to 115° F
FACE PANEL COMPONENTS
RX 1–2
Indicates receiving data from ports 1–2
TX 1–2
Indicates transmitting data to ports 1–2
RS485 1–2
Indicates RS485 mode of ports 1–2
status
Indicates power status and connection to
controllers
link/act
Ethernet link and activity indicator
reset
Multifunctional button (reboot, reset, bootload-
er)
TERMINAL PANELS
LAN
Ethernet network and PoE power connector
PWR
Power supply terminals (12–24 VDC)
1–2
Serial ports terminals:
GND
– Ground contact of RS232 interface,
isolated from
PWR “–”
contact
RX/TX
– RS232 RXD and TXD signals
A/RTS
– RS232 RTS or RS485 A(–) signal
B/CTS
– RS232 CTS or RS485 B(+) signal
Operating humidity
5 to 80% RH
non-condensing
Enclosure
5M DIN rail box,
UL94-V0 flame retardant PC
Dimensions (HWD)
90 mm x 88 mm x 58 mm
3.54” x 3.46” x 2.28”
Weight
170 g
0.37 lbs
Supported data exchange
protocols
NetString
Point-to-Point
ECM-RS2D
RS232/RS485/DMX512 Ports Module
Quick Reference Guide
(revision 2.30 for H/W Rev.E)
1
2
3
4
5
6
7
8
9
10 11 12
LAN
SPECIFICATIONS
The ECM-RS2D module is designed to control any devices with
RS232/RS485 interface as well as be DMX512 controller.
The module is a bidirectional gateway between physical interface
RS232/RS485 and Ethernet network and supports multiple TCP/
IP connections for each serial port.
The device has 2 independent isolated serial ports.
The control, data exchange and configuration are all handled via
TCP/IP protocol.
The ECM-RS2D version is designed to be installed on a standard
35 mm DIN-rail.