5. Servo operating
4-25
4.6.2. Absolute value encoder initialization
1) When the absolute value encoder requires initialization
- During first operation
- When the encoder cable is separate from the servo drive
- After replacing the battery
- When the absolute encoder related alarm is generated
2) Absolute value encoder initialization (reset) method
- 17bit serial absolute value encoder: When it sets the origin by itself, set the parameter
(P01-20) to “ON” and it will change to “ON =>OFF” to initialize the current position. (Multi-
Turn data reset). When the absolute value related alarm is generated, execute alarm reset
by using alarm reset contact point (ALMRST).
- When it sets the origin by itself, set the parameter (P01-20) to “ON” and it will change to
“ON =>OFF” to initialize the current position. Or connect the power to encoder terminal
ERST (CN2-20) and Vcc terminal (CN2-19) for more than 4 seconds.
Содержание FDA7000 Series
Страница 42: ...1 Model check and handling 1 35...
Страница 57: ...2 Wiring and connection 2 14 Drawing C Order Code Please contact our sales office...
Страница 130: ...3 Parameter setting 3 51...
Страница 167: ...5 Servo operating 5 10...
Страница 188: ...8 External view 8 2 External view B CN1 CN3 CN2 External view C...
Страница 189: ...8 External view 8 3 External view D External view E...
Страница 190: ...8 External view 8 4 External view F External view G...
Страница 192: ...8 External view 8 6 External view I External view J...
Страница 193: ...8 External view 8 7 External view K External view L...
Страница 194: ...8 External view 8 8 External view M...
Страница 195: ...8 External view 8 9...