Softmaster
®
ROE 2 / S5
Additional manual for option S5
Microprocessor controllers for reverse osmosis plants
Страница 1: ...Softmaster ROE 2 S5 Additional manual for option S5 Microprocessor controllers for reverse osmosis plants ...
Страница 2: ...on Type of contact Test time Action Pressure monitoring in front of the pump programmable normally closed normally open programmable 01 99 seconds programmable Test time 1 99 sec Not programmable Switch off the plant Continuous alarm after switch off Entry in the error list Only for controller operation with level transmitter Function Type of contact Test time Action Pressure monitoring in front o...
Страница 3: ...e of the number of restart attempts Error message Low water pressure The pressure switch in front of the pressure pump for the dry running protection has triggered The plant has been switched off after the programmed delay time Delay LP Restart the plant with the RUN STOP key If water is still low the plant is switched off again after the delay time If the system has been switched off via the dry ...