Remove the access panel
WARNING:
To reduce the risk of personal injury from hot surfaces, allow the drives and the internal
system components to cool before touching them.
CAUTION:
For proper cooling, do not operate the server without the access panel, baffles,
expansion slot covers, or blanks installed. If the server supports hot-plug components, minimize the
amount of time the access panel is open.
CAUTION:
To prevent damage to electrical components, properly ground the server before
beginning any installation procedure. Improper grounding can cause electrostatic discharge.
Procedure
on page 29.
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Disconnect all peripherals cables from the server.
4.
If a Kensington security cable is installed, disconnect it from the rear panel. See the security cable
documentation for instructions.
5.
Do one of the following:
• Server in rack mode:
Remove the server from the rack
on page 30.
Position the tower server for hardware configuration
on page 31.
6.
Remove the access panel:
32
Removal and replacement procedures