Specifications
UPS physical specifications
Parameter
Value
Height
25.9 (10.19in)
Depth
76.2cm (30.0in)
Width
43.9cm (17.3in)
Weight
89.7kg (197.7lb)
ERM physical specifications
Parameter
Value
Height
13.0cm (5.1in)
Depth
76.2cm (30.0in)
Width
43.9cm (17.3in)
Weight
63.45kg (139.88lb)
UPS input specifications
UPS model
Utility voltage
frequency (Hz)
Available settings
utility voltage (VAC)
Branch circuit
rating (A)
Line cord
G2 R8000
50/60
200/208/220/230/240
/250
40/38.4/36.3/34.7/33.
3/32
Hardwired power
connection
UPS output specifications
UPS model
Output receptacles
G2 R8000 NA/JPN
4x L6-20R, 2x L6-30R, Hardwired
G2 R8000 INTL
6x C19, 2x IEC 32A Pigtail (253”/0”), Hardwired
Power protection specifications
UPS model
VA
Nominal power rating
(W)
Output voltage setting
G2 R8000
8000
7200
200/208/220/230/240/25
0
Specifications
35